Frames R3…R8: 2 ms (typical), 5 ms (maximum)
•
Fault detection time: Channels in different states for longer than 200 ms
•
Fault reaction time: Fault detection time + 10 ms
•
Indication delays:
•
STO fault indication (parameter
31.22
) delay: < 500 ms
•
STO warning indication (parameter
31.22
) delay: < 1000 ms
■
Abbreviations
Description
Reference
Abbr.
Classification of the safety-related parts of a control system in respect
of their resistance to faults and their subsequent behavior in the fault
condition, and which is achieved by the structural arrangement of the
parts, fault detection and/or by their reliability. The categories are: B,
1, 2, 3 and 4.
EN ISO 13849-1
Cat.
Common cause failure (%)
EN ISO 13849-1
CCF
Diagnostic coverage
EN ISO 13849-1
DC
Hardware fault tolerance
IEC 61508
HFT
Mean time to dangerous failure: (Total number of life units) / (Number
of dangerous, undetected failures) during a particular measurement
interval under stated conditions
EN ISO 13849-1
MTTF
D
Average probability of dangerous failure on demand, that is, mean
unavailability of a safety-related system to perform the specified safety
function when a demand occurs
IEC 61508
PFD
avg
Average frequency of dangerous failures per hour, that is, average
frequency of a dangerous failure of a safety related system to perform
the specified safety function over a given period of time
IEC 61508
PFH
Performance level. Levels a…e correspond to SIL
EN ISO 13849-1
PL
Systematic capability
IEC 61508
SC
Safe failure fraction (%)
IEC 61508
SFF
Safety integrity level (1…3)
IEC 61508
SIL
Maximum SIL (level 1…3) that can be claimed for a safety function
or subsystem
IEC/EN 62061
SILCL
Safe torque off
IEC/EN 61800-5-2
STO
Proof test interval. T
1
is a parameter used to define the probabilistic
failure rate (PFH or PFD) for the safety function or subsystem. Per-
forming a proof test at a maximum interval of T
1
is required to keep
the SIL capability valid. The same interval must be followed to keep
the PL capability (EN ISO 13849) valid.
IEC 61508-6
T
1
See also section Maintenance.
Mission time: the period of time covering the intended use of the safety
function/device. After the mission time elapses, the safety device must
be replaced. Note that any T
M
values given cannot be regarded as a
guarantee or warranty.
EN ISO 13849-1
T
M
The Safe torque off function 161
Summary of Contents for ACQ80-04 Series
Page 1: ...ABB DRIVES FOR WATER ACQ80 04 drives 0 75 to 160 kW 1 0 to 215 hp Hardware manual...
Page 2: ......
Page 4: ......
Page 18: ...18...
Page 24: ...24...
Page 38: ...38...
Page 50: ...50...
Page 64: ...64...
Page 98: ...98...
Page 110: ...110...
Page 140: ...Frame R3 IP20 140 Dimension drawings...
Page 146: ...146...
Page 162: ...162...
Page 168: ......