Electrical installation 75
Frames R4…R8
To disconnect the internal EMC filter or ground-to-phase varistor, if needed, do as
follows:
1. Switch off the power from the drive.
2. Open the cover, if not already opened. For frames R4…R6, see page
82
. For
frames R6…R8, see page
86
.
3. To disconnect the internal EMC filter, remove the two EMC screws.
4. To disconnect the ground-to-phase varistor, remove the varistor screw.
R4
3
3
4
3
3
4
R5
3
3
4
3
3
4
R5
Electrical installation 75
Frames R4…R8
To disconnect the internal EMC filter or ground-to-phase varistor, if needed, do as
follows:
1. Switch off the power from the drive.
2. Open the cover, if not already opened. For frames R4…R6, see page
82
. For
frames R6…R8, see page
86
.
3. To disconnect the internal EMC filter, remove the two EMC screws.
4. To disconnect the ground-to-phase varistor, remove the varistor screw.