तकनीकी
डेटा
125
Frame R0
Frames R1...R3
Frames R4...R8
T
1.00
0.90
k
0.80
0.85
0.95
0.95
-15 °C
5 °F
...
50 °C
104 °F
55 °C
131 °F
T
1.00
0.90
k
0.80
0.85
0.95
0.90
-15 °C
5 °F
...
50 °C
104 °F
55 °C
131 °F
60 °C
140 °F
T
1.00
0.90
k
0.80
0.85
0.95
0.
90
-15 °C
5 °F
...
40 °C
104 °F
45 °C
113 °F
50 °C
122 °F
■
Switching frequency derating
The output current is calculated by multiplying the current given in the rating table by the
derating factor given in the table below.
Note:
If you change the minimum switching frequency with parameter 97.02 Minimum switching
frequency, derate according to the table below. Changing parameter 97.01 Switching
frequency reference does not require derating.
Derating factor of the min. switch frequency
Frame size
12kHz
8kHz
4kHz
2kHz
0.48
0.65
1
1
R0
0.5
0.67
1
1
R1
0.5
0.67
1
1
R2
114 Technical data