BIO-01 I/O extension module 157
Electrical installation
Refer to
Electrical installation
on page
55
. If you configure the inputs, set up the
wiring accordingly. The BIO-01 module has removable spring clamp terminals. Use
ferrules on the multistranded cables before assembly.
Sample wiring with the ABB standard macro:
Start-up
The BIO-01 module is automatically identified by the drive firmware. To configure the
inputs refer to the
ACS480 firmware manual
(3AXD50000047399 [English])
.
Terminals
External sample connection
Description
Base
unit
Internal connection
Aux. voltage output and prog. digital input
+24V
Aux. 24 V DC, max. 200 mA
X
DGND
Aux. voltage output common
X
DCOM
Digital input common for all
X
DI1
Stop (0)/Start (1)
X
DI2
Forward (0)/Reverse (1)
X
Digital and analog I/O extension BIO-01
DI3
Constant frequency/speed selection
DI4
Constant frequency/speed selection
DI5
Ramp set 1 (0)/Ramp set 2 (1)
DO1
Not configured
AI1
Output frequency/speed ref: 0...10 V
+10V
Ref. v10 V DC (max. 10 mA)
GND
Analog circuit common / DO common
SCR
Signal cable shield / DO screen
Safe torque off (STO)
SGND
Safe torque off. Factory connection.
Both circuits must be closed for the
drive to start.
X
IN1
X
IN2
X
OUT1
X
Start-up
After connecting the device, restart the drive for auto detection of the BIO-01 module. To
configure the inputs manually, refer to the ACQ80-04 firmware manual
(3AXD50000170654[English].
Technical data
■
Control connection data
For BIO-01 electrical data, see chapter
.
166 BIO-01 I/O extension module
Summary of Contents for ACQ80-04 Series
Page 1: ...ABB DRIVES FOR WATER ACQ80 04 drives 0 75 to 160 kW 1 0 to 215 hp Hardware manual...
Page 2: ......
Page 4: ......
Page 18: ...18...
Page 24: ...24...
Page 38: ...38...
Page 50: ...50...
Page 64: ...64...
Page 98: ...98...
Page 110: ...110...
Page 140: ...Frame R3 IP20 140 Dimension drawings...
Page 146: ...146...
Page 162: ...162...
Page 168: ......