Parameters 125
Selects the way the motor is stopped when an
emergency stop command is received.
The source of the emergency stop signal is
selected by parameter
.
Note:
After the drive stops, you can restore the
emergency stop signal and switch the start
signal from 0 to 1 to restart the drive. This is not
required if
is set to
.
Ramp stop
(Off1)
With the drive running:
• 1 = Normal operation.
• 0 = Normal stop along the standard
deceleration ramp for the below reference
types:
•
in speed mode
in frequency
mode
With the drive stopped:
• 1 = Starting allowed.
• 0 = Starting not allowed.
0
Coast stop
(Off2)
With the drive running:
• 1 = Normal operation.
• 0 = Stop by coasting.
The drive can be restarted by restoring the
start interlock signal and switching the start
signal from 0 to 1.
With the drive stopped:
• 1 = Starting allowed.
• 0 = Starting not allowed.
1
Eme ramp stop
(Off3)
With the drive running:
• 1 = Normal operation
• 0 = Stop by ramping along emergency stop
ramp defined by parameter
After the drive has stopped, it can be restarted
by removing the emergency stop signal and
switching the start signal from 0 to 1.
With the drive stopped:
• 1 = Starting allowed
• 0 = Starting not allowed
2
No.
Name/Value
Description
Def/
FbEq16
Summary of Contents for ACQ80
Page 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Page 2: ... Related documents are listed on page 13 ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Startup control with I O and ID run ...
Page 34: ...34 Using the control panel ...
Page 74: ...74 Program features ...
Page 78: ...78 Control macros ...
Page 380: ...380 Fieldbus control through a fieldbus adapter ...
Page 384: ...384 Parameterization with Drive Composer ...
Page 388: ...388 Parameterization with Automation builder drive manager ...