200 Parameters
Selects the source of process PID set 1 activation.
Off
Set 1 PID activation source is Off.
0
On
Set 1 PID activation source is On.
1
DI1
Digital input DI1 (
, bit 0).
3
DI2
Digital input DI2 (
, bit 1).
4
DI3
Digital input DI3 (
, bit 2).
5
DI4
Digital input DI4 (
, bit 3).
6
DI5
Digital input DI5 (
, bit 4).
7
DI6
Digital input DI6 (
, bit 5).
8
DIO1
Digital input/output DIO1.
9
DIO2
Digital input/output DIO2.
10
Source selection (see
on
page
-
Actual setpoint scaling. See parameter
.
0.00
-200000.00…
200000.00 PID
customer units
Scaling.
1 = 1 PID
customer
unit
Shows value of the internal setpoint.
This parameter is read-only.
-
-200000.00…
200000.00
Process PID internal setpoint.
1 = 1
No.
Name/Value
Description
Def/
FbEq16