Parameters 217
Shows protocol ID and revision.
This parameter is read-only.
-
Protocol ID and revision.
1 = 1
Defines the node address of the drive on the
fieldbus link.
Values 1…247 are allowable. Two devices with the
same address are not allowed on-line.
Changes to this parameter take effect after the
control unit is rebooted or the new settings
validated by parameter
).
1
0…255
Node address (values 1…247 are allowed).
1 = 1
Selects the transfer rate of the fieldbus link.
Changes to this parameter take effect after the
control unit is rebooted or the new settings
validated by parameter
).
Autodetect
Baud rate detected automatically
0
4.8 kbps
4.8 kbit/s.
1
9.6 kbps
9.6 kbit/s.
2
19.2 kbps
19.2 kbit/s.
3
38.4 kbps
38.4 kbit/s.
4
57.6 kbps
57.6 kbit/s.
5
76.8 kbps
76.8 kbit/s.
6
115.2 kbps
115.2 kbit/s.
7
Selects the type of parity bit and number of stop
bits.
Changes to this parameter take effect after the
control unit is rebooted or the new settings
validated by parameter
).
8 NONE 1
Eight data bits, no parity bit, one stop bit.
0
8 NONE 2
Eight data bits, no parity bit, two stop bits.
1
8 EVEN 1
Eight data bits, even parity bit, one stop bit.
2
8 ODD 1
Eight data bits, odd parity bit, one stop bit.
3
Takes changed EFB settings in use, or activates
silent mode.
Enabled
Normal operation.
0
No.
Name/Value
Description
Def/
FbEq16
Summary of Contents for ACQ80
Page 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Page 2: ... Related documents are listed on page 13 ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Startup control with I O and ID run ...
Page 34: ...34 Using the control panel ...
Page 74: ...74 Program features ...
Page 78: ...78 Control macros ...
Page 380: ...380 Fieldbus control through a fieldbus adapter ...
Page 384: ...384 Parameterization with Drive Composer ...
Page 388: ...388 Parameterization with Automation builder drive manager ...