256 Parameters
Clears all events from the drive’s fault and event
logs.
0
0…1
1 = 1
Enables/disables the adaptive program (if
present).
See also section
(page
No
Adaptive program enabled.
0
Yes
Adaptive program disabled.
1
Enables a Modbus user to access a select set of
parameters using legacy register numbering.
See the supported parameters in section
on page
Disable
Using legacy register numbering disabled.
0
Enable
Using legacy register numbering enabled.
This selection sets parameter
. Only 16-bit addressing is used,
and only 16-bit data is used for reading and
writing.
16-bit values (groups 1…99, indexes 1…99):
Register address = 40000 + 100 × parameter
group + parameter index. For example,
parameter 22.80 would be mapped to register
40000 + 2200 + 80 = 42280.
1
Enables using a legacy control profile. Currently
only EFB supports legacy profiles.
Not selected
EFB: Control profile selected with
used.
0
DCU
Legacy DCU profile used.
1
ABB drives
ABB drives profile used.
2
ABB drives
limited
Legacy ABB drives limited profile used.
3
No.
Name/Value
Description
Def/
FbEq16
Summary of Contents for ACQ80
Page 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Page 2: ... Related documents are listed on page 13 ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Startup control with I O and ID run ...
Page 34: ...34 Using the control panel ...
Page 74: ...74 Program features ...
Page 78: ...78 Control macros ...
Page 380: ...380 Fieldbus control through a fieldbus adapter ...
Page 384: ...384 Parameterization with Drive Composer ...
Page 388: ...388 Parameterization with Automation builder drive manager ...