Parameters 267
Defines the cosphi of the motor for a more
accurate motor model. The value is not
obligatory, but is useful with an asynchronous
motor, especially when performing a standstill
identification run. With a permanent magnet or
synchronous reluctance motor, this value is not
needed.
Notes:
• Do not enter an estimated value. If you do not
know the exact value, leave the parameter at
zero.
• This parameter cannot be changed while the
drive is running.
0.00
0.00…1.00
Cosphi of the motor.
100 = 1
Defines the nominal motor shaft torque for a
more accurate motor model. Not obligatory. The
unit is selected by parameter
.
Note:
This parameter cannot be changed while
the drive is running.
0.000
N·m or
lb·ft
0.000…
4000000.000
N·m or 0.000…
2950248.597
lb·ft
Nominal motor torque.
1 = 100
unit
No.
Name/Value
Description
Def/
FbEq16
Summary of Contents for ACQ80
Page 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Page 2: ... Related documents are listed on page 13 ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Startup control with I O and ID run ...
Page 34: ...34 Using the control panel ...
Page 74: ...74 Program features ...
Page 78: ...78 Control macros ...
Page 380: ...380 Fieldbus control through a fieldbus adapter ...
Page 384: ...384 Parameterization with Drive Composer ...
Page 388: ...388 Parameterization with Automation builder drive manager ...