Startup, control with I/O and ID run 29
Pre-check
WARNING!
The motor will run at up to approximately 50…80% of the
nominal speed during the ID run. The motor will rotate in the forward
direction.
Make sure that it is safe to run the motor before performing the
ID run.
Do not do ID run on a rotating motor. Make sure that the motor is
stopped before starting the ID run.
De-couple the motor from the driven equipment
Check that the values of the motor data parameters are equivalent to those on the
motor nameplate.
Check that the STO circuit is closed.
If parameter values (from group
to group
) are
changed before the ID run, check that the new settings meet the following
conditions:
< 0 rpm
= motor rated speed (Normal ID run procedure needs the
motor to be run at 100% speed.)
> 0.5 x motor nominal current
> 50%
Make sure that the control panel is in local control (text Local shown at the top
left). Press key
to switch between local and remote control.
ID run
Go to the
Main
menu by pressing
(
Menu
) in the Home view.
Press .
Select
Parameters
and press
(
Select
)
(or ).
Loc/Rem
Summary of Contents for ACQ80
Page 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Page 2: ... Related documents are listed on page 13 ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Startup control with I O and ID run ...
Page 34: ...34 Using the control panel ...
Page 74: ...74 Program features ...
Page 78: ...78 Control macros ...
Page 380: ...380 Fieldbus control through a fieldbus adapter ...
Page 384: ...384 Parameterization with Drive Composer ...
Page 388: ...388 Parameterization with Automation builder drive manager ...