310 Fault tracing
A580 PU
communication
Communication errors
between drive control
unit and power unit.
Check connections between
drive control unit and power unit
and value of parameter
A581
Fan
Cooling fan feedback
missing.
Check the auxiliary code to
identify the fan. Code 0 denotes
main fan 1. Other codes (format
XYZ): “X” specifies state code (1:
ID run, 2: normal). “Y” = 0, “Z”
specifies the index of the fan (1:
Main fan 1, 2: Main fan 2, 3: Main
fan 3). Check fan operation and
connection. Replace fan if faulty.
A582 Auxiliary fan
missing
An auxiliary cooling fan
(connected to the fan
connectors on the
control board) is stuck or
disconnected.
Check the auxiliary code.
Check auxiliary fan(s) and
connection(s).
Replace faulty fan.
Make sure the front cover of the
drive is in place and tightened. If
the commissioning of the drive
requires that the cover is off,
this warning will be generated
even if the corresponding fault is
defeated. See fault
(page
).
0001
Auxiliary fan 1 missing.
0002
Auxiliary fan 2 missing.
A591
Drive HW
initialization.
Drive hardware setup is
initializing.
1 - Initializing HW
settings for the first
time.
See auxiliary code.
A5A0 Safe torque off
Programmable
warning:
Safe torque off function
is active, ie safety circuit
signal(s) connected to
connector STO is lost.
Check safety circuit
connections. For more
information, chapter
The Safe
torque off function
in the
Hardware manual
of the drive
and description of parameter
(page
Check the value of parameter
Code
(hex)
Warning / Aux.
code
(
aux code visible
only on assistant
control panel and drive
composer)
Cause
What to do
Summary of Contents for ACQ80
Page 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Page 2: ... Related documents are listed on page 13 ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Startup control with I O and ID run ...
Page 34: ...34 Using the control panel ...
Page 74: ...74 Program features ...
Page 78: ...78 Control macros ...
Page 380: ...380 Fieldbus control through a fieldbus adapter ...
Page 384: ...384 Parameterization with Drive Composer ...
Page 388: ...388 Parameterization with Automation builder drive manager ...