320 Fault tracing
D50C Maximum flow
protection
Programmable
warning:
Actual flow is exceeded
the defined warning
level.
Check the system for leakages.
Check flow protection settings
in parameters
,
, and
D50D Minimum flow
protection
Programmable
warning:
Actual flow is below the
defined warning level.
Check that the inlet and outlet
valves are open.
Check flow protection settings
in parameters
,
, and
D50E Outlet minimum
pressure
Programmable
warning:
Measured outlet
pressure is below the
defined warning limit.
Check the pump outlet for
leakages. Check the
configuration of outlet pressure
protection.
See parameters
.
D50F Outlet maximum
pressure
Programmable
warning:
Measured outlet
pressure is above the
defined warning limit.
Check the pump outlet for
blockages or closed valve.
Check the configuration of
outlet pressure protection.
See parameters
and
D510 Inlet minimum
pressure
Programmable
warning:
Measured inlet pressure
is below the defined
warning level.
Check the pump inlet for
blockages or closed valve.
Check the configuration of inlet
pressure protection.
See parameters
Code
(hex)
Warning / Aux.
code
(
aux code visible
only on assistant
control panel and drive
composer)
Cause
What to do
Summary of Contents for ACQ80
Page 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Page 2: ... Related documents are listed on page 13 ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Startup control with I O and ID run ...
Page 34: ...34 Using the control panel ...
Page 74: ...74 Program features ...
Page 78: ...78 Control macros ...
Page 380: ...380 Fieldbus control through a fieldbus adapter ...
Page 384: ...384 Parameterization with Drive Composer ...
Page 388: ...388 Parameterization with Automation builder drive manager ...