Fieldbus control through the embedded fieldbus interface (EFB) 349
Modern Modbus master devices typically provide a means to access the full
range of 65536 Modbus holding registers. One of these methods is to use 6-
digit decimal addresses from 400001 to 465536. This manual uses 6-digit
decimal addressing to represent Modbus holding register addresses.
Modbus master devices that are limited to the 5-digit decimal addressing may
still access registers 400001 to 409999 by using 5-digit decimal addresses
40001 to 49999. Registers 410000-465536 are inaccessible to these masters.
See parameter
.
Note:
Register addresses of 32-bit parameters cannot be accessed by using 5-
digit register numbers.