356 Fieldbus control through the embedded fieldbus interface (EFB)
Status Word for the DCU Profile
The embedded fieldbus interface writes the drive Status Word bits 0 to 15 to
the fieldbus Status Word as is. Bits 16 to 32 of the drive Status Word are not in
use.
Bit
Name
Value
State/Description
0
READY
1
Drive is ready to receive the start command.
0
Drive is not ready.
1
D
1
External run enable signal is active.
0
External run enable signal is not active.
2
Reserved for
D_TO_ROTATE
Not yet implemented.
3
RUNNING
1
Drive is modulating.
0
Drive is not modulating.
4
ZERO_SPEED
1
Drive is at zero speed.
0
Drive is not at zero speed.
5
ACCELERATING
1
Drive speed is increasing.
0
Drive speed is not increasing.
6
DECELERATING
1
Drive speed is decreasing.
0
Drive speed is not decreasing.
7
AT_SETPOINT
1
Drive is at setpoint.
0
Drive is not at setpoint.
8
LIMIT
1
Drive operation is limited.
0
Drive operation is not limited.
9
SUPERVISION
1
Actual value (speed, frequency or torque) is above
a limit. Limit is set with parameters 46.31…46.33
0
Actual value (speed, frequency or torque) is within
limits.
10
REVERSE_REF
1
Drive reference is in the reverse direction.
0
Drive reference is in the forward direction
11
REVERSE_ACT
1
Drive is running in the reverse direction
0
Drive is running in the forward direction
12
PANEL_LOCAL
1
Panel/keypad (or PC tool) is in local control mode.
0
Panel/keypad (or PC tool) is not in local control
mode.
13
FIELDBUS_LOCAL 1
Fieldbus is in local control mode.
0
Fieldbus is not in local control mode.
14
EXT2_ACT
1
External control location EXT2 is active.
0
External control location EXT1 is active.
Summary of Contents for ACQ80
Page 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Page 2: ... Related documents are listed on page 13 ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Startup control with I O and ID run ...
Page 34: ...34 Using the control panel ...
Page 74: ...74 Program features ...
Page 78: ...78 Control macros ...
Page 380: ...380 Fieldbus control through a fieldbus adapter ...
Page 384: ...384 Parameterization with Drive Composer ...
Page 388: ...388 Parameterization with Automation builder drive manager ...