Parameters 117
Selects the unit for readings and settings related
to analog input AO1.
Note: In firmware ASCL2 and ASCL4), this setting
must match the corresponding hardware setting
on the drive control unit. See chapter
Electrical
installation
, section
Switches
in the
Hardware
manual
of the drive and the default control
connections for the macro in use in chapter
(page
). Control board reboot
(either by cycling the power or through
parameter
) is required to
validate any changes in the hardware settings.
V
Volts.
2
mA
Milliamperes.
10
Defines the filtering time constant for analog
output AO1.
0.100 s
0.000 …
30.000 s
Filter time constant.
1000 = 1 s
No.
Name/Value
Description
Def/
FbEq16
63
%
100
T
t
O = I × (1 - e
-t/T
)
I = filter input (step)
O = filter output
t
= time
T = filter time constant
Unfiltered signal
Filtered signal