266 Parameters
Defines the nominal motor voltage supplied to
the motor. This setting must match the value on
the rating plate of the motor.
Notes
:
• With permanent magnet motors, the nominal
voltage is the BackEMF voltage at nominal
speed of the motor. If the voltage is given as
voltage per rpm, e.g. 60 V per 1000 rpm, the
voltage for a nominal speed of 3000 rpm is
3 × 60 V = 180 V.
• The stress on the motor insulation is always
dependent on the drive supply voltage. This
also applies to the case where the motor
voltage rating is lower than that of the drive
and the supply.
• This parameter cannot be changed while the
drive is running.
400.0 V
69.2...830.0 V
Nominal voltage of the motor.
10 = 1 V
Defines the nominal motor frequency. This
setting must match the value on the rating plate
of the motor.
Note:
This parameter cannot be changed while
the drive is running.
50.0 Hz
0.0…500.0 Hz
Nominal frequency of the motor.
10 = 1 Hz
Defines the nominal motor speed. The setting
must match the value on the rating plate of the
motor.
Note:
This parameter cannot be changed while
the drive is running.
1430 rpm
0…30000 rpm
Nominal speed of the motor.
1 = 1 rpm
Defines the nominal motor power. The setting
must match the value on the rating plate of the
motor. If multiple motors are connected to the
drive, enter the total power of the motors. The
unit is selected by parameter
.
Note:
This parameter cannot be changed while
the drive is running.
0.75 kW
0.00…
10000.00 kW or
0.00…
13404.83 hp
Nominal power of the motor.
1 = 1 unit
No.
Name/Value
Description
Def/
FbEq16
Summary of Contents for ACQ80
Page 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Page 2: ... Related documents are listed on page 13 ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Startup control with I O and ID run ...
Page 34: ...34 Using the control panel ...
Page 74: ...74 Program features ...
Page 78: ...78 Control macros ...
Page 380: ...380 Fieldbus control through a fieldbus adapter ...
Page 384: ...384 Parameterization with Drive Composer ...
Page 388: ...388 Parameterization with Automation builder drive manager ...