Additional parameter data 275
Parameter groups 1…9
No.
Name
Type
Range
Unit
FbEq32
01 Actual values
01.01
Motor speed used
-30000.00…30000.00 rpm
100 = 1 rpm
01.02
Motor speed estimated
-30000.00…30000.00 rpm
100 = 1 rpm
01.03
Motor speed %
-1000.00…1000.00
%
100 = 1%
01.06 Output frequency
-500.00…500.00
Hz
100 = 1 Hz
01.07
Motor current
0.00…30000.00
A
100 = 1 A
01.08 Motor current % of
motor nom
0.0…1000.0
%
10 = 1%
01.09 Motor current % of drive
nom
0.0…1000.0
%
10 = 1%
01.10
Motor torque
-1600.0…1600.0
%
10 = 1%
01.11
DC voltage
0.00…2000.00
V
100 = 1 V
01.13
Output voltage
0…2000
V
1 = 1 V
01.14
Output power
-32768.00…32767.00
kW
100 = 1 unit
01.15
Output power % of
motor nom
-300.00…300.00
%
100 = 1%
01.17
Motor shaft power
-32768.00…32767.00
kW or
hp
100 = 1 unit
01.18
Inverter GWh counter
0…65535
GWh
1 = 1 GWh
01.19
Inverter MWh counter
0…1000
MWh
1 = 1 MWh
01.20
Inverter kWh counter
0…1000
kWh
1 = 1 kWh
01.24
Flux actual %
0…200
%
1 = 1%
01.30
Nominal torque scale
0.000…4000000
N·m
1000 = 1
unit
01.50
Current hour kWh
0.00…1000000.00
kWh
100 = 1 kWh
01.51
Previous hour kWh
0.00…1000000.00
kWh
100 = 1 kWh
01.52
Current day kWh
0.00…1000000.00
kWh
100 = 1 kWh
01.53
Previous day kWh
0.00…1000000.00
kWh
100 = 1 kWh
01.54 Cumulative inverter
energy
0…1000000.00
kWh
100 = 1 kWh
01.55
Inverter GWh counter
(resettable)
-200000000.0…
200000000.0
kWh
1 = 1 kWh
01.56 Inverter MWh counter
(resettable)
0…65535
GWh
1 = 1 kWh
01.57
Inverter kWh counter
(resettable)
0…1000
MWh
1 = 1 kWh
01.58 Cumulative inverter
energy (resettable)
0…1000
kWh
1 = 1 kWh
01.61
Abs motor speed used
0.00…30000.00
rpm
100 = 1 rpm
Summary of Contents for ACQ80
Page 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Page 2: ... Related documents are listed on page 13 ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Startup control with I O and ID run ...
Page 34: ...34 Using the control panel ...
Page 74: ...74 Program features ...
Page 78: ...78 Control macros ...
Page 380: ...380 Fieldbus control through a fieldbus adapter ...
Page 384: ...384 Parameterization with Drive Composer ...