352 Fieldbus control through the embedded fieldbus interface (EFB)
Control Word for the DCU Profile
The embedded fieldbus interface writes the fieldbus Control Word as is to the
drive Control Word bits 0 to 15. Bits 16 to 32 of the drive Control Word are not in
use.
7
RESET
0=>1
Fault reset if an active fault exists. Proceed to
SWITCH-ON INHIBITED
.
Note:
This bit is effective only if the fieldbus interface
is set as the source for this signal by drive
parameters.
0
Continue normal operation.
8...9 Reserved
10
REMOTE_
CMD
1
Fieldbus control d.
0
Control Word <> 0 or Reference <> 0: Retain last
Control Word and Reference.
Control Word = 0 and Reference = 0: Fieldbus control
d. Reference and deceleration/acceleration ramp are
locked.
11
EXT_CTRL_
LOC
1
Select External Control Location EXT2. Effective if the
control location is parameterized to be selected from
the fieldbus.
0
Select External Control Location EXT1. Effective if the
control location is parameterized to be selected from
the fieldbus.
12
USER_0
Writable control bits that can be combined with drive
logic for application-specific functionality.
13
USER_1
14
USER_2
15
USER_3
Bit
Name
Value State/Description
0
STOP
1
Stop according to the Stop Mode parameter or the
stop mode request bits (7…9).
0
(no op)
1
START
1
Start the drive.
0
(no op)
Bit
Name
Value STATE/Description
Summary of Contents for ACQ80
Page 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Page 2: ... Related documents are listed on page 13 ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Startup control with I O and ID run ...
Page 34: ...34 Using the control panel ...
Page 74: ...74 Program features ...
Page 78: ...78 Control macros ...
Page 380: ...380 Fieldbus control through a fieldbus adapter ...
Page 384: ...384 Parameterization with Drive Composer ...
Page 388: ...388 Parameterization with Automation builder drive manager ...