364 Fieldbus control through the embedded fieldbus interface (EFB)
Coils (0xxxx reference set)
Coils are 1-bit read/write values. Control Word bits are exposed with this data
type. The table below summarizes the Modbus coils (0xxxx reference set). Note
that the references are 1-based index which match the address transmitted on
the wire.
Reference ABB Drives profile
DCU Profile
000001
OFF1_CONTROL
STOP
000002
OFF2_CONTROL
START
000003
OFF3_CONTROL
Reserved
000004
INHIBIT_OPERATION
Reserved
000005
RAMP_OUT_ZERO
RESET
000006
RAMP_HOLD
EXT2
000007
RAMP_IN_ZERO
RUN_DISABLE
000008
RESET
STOPMODE_RAMP
000009
Reserved
Reserved
000010
Reserved
Reserved
000011
REMOTE_CMD
Reserved
000012
EXT_CTRL_LOC
RAMP_OUT_ZERO
000013
USER_0
RAMP_HOLD
000014
USER_1
RAMP_IN_ZERO
000015
USER_2
Reserved
000016
USER_3
Reserved
000017
Reserved
FB_LOCAL_CTL
000018
Reserved
FB_LOCAL_REF
000019
Reserved
Reserved
000020
Reserved
Reserved
000021
Reserved
Reserved
000022
Reserved
Reserved
000023
Reserved
USER_0
000024
Reserved
USER_1
000025
Reserved
USER_2
000026
Reserved
USER_3
000027
Reserved
Reserved
000028
Reserved
Reserved
000029
Reserved
Reserved
000030
Reserved
Reserved
000031
Reserved
Reserved
000032
Reserved
Reserved
Summary of Contents for ACQ80
Page 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Page 2: ... Related documents are listed on page 13 ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Startup control with I O and ID run ...
Page 34: ...34 Using the control panel ...
Page 74: ...74 Program features ...
Page 78: ...78 Control macros ...
Page 380: ...380 Fieldbus control through a fieldbus adapter ...
Page 384: ...384 Parameterization with Drive Composer ...
Page 388: ...388 Parameterization with Automation builder drive manager ...