368 Fieldbus control through the embedded fieldbus interface (EFB)
Error code registers (holding registers 400090…400100)
These registers contain information about the last query. The error register is
cleared when a query has finished successfully.
Reference Name
Description
400090
Reset Error Registers
1 = Reset internal error registers (91…95). 0 = Do
nothing.
400091
Error Function Code
Function code of the failed query.
400092
Error Code
Set when exception code 04h is generated (see
table above).
• 00h No error
• 02h Low/High limit exceeded
• 03h Faulty Index: Unavailable index of an array
parameter
• 05h Incorrect Data Type: Value does not match
the data type of the parameter
• 65h General Error: Undefined error when
handling query
400093
Failed Register
The last register (discrete input, coil, input
register or holding register) that failed to be read
or written.
400094
Last Register Written
Successfully
The last register (discrete input, coil, input
register or holding register) that was written
successfully.
400095
Last Register Read
Successfully
The last register (discrete input, coil, input
register or holding register) that was read
successfully.
Summary of Contents for ACQ80
Page 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Page 2: ... Related documents are listed on page 13 ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Startup control with I O and ID run ...
Page 34: ...34 Using the control panel ...
Page 74: ...74 Program features ...
Page 78: ...78 Control macros ...
Page 380: ...380 Fieldbus control through a fieldbus adapter ...
Page 384: ...384 Parameterization with Drive Composer ...
Page 388: ...388 Parameterization with Automation builder drive manager ...