Fieldbus control through a fieldbus adapter 371
Basics of the fieldbus control interface
The cyclic communication between a fieldbus system and the drive consists of
16- or 32-bit input and output data words. The drive is able to support a
maximum of 12 data words (16 bits) in each direction.
Data transmitted from the drive to the fieldbus controller is defined by
. The data transmitted
from the fieldbus controller to the drive is defined by parameters
DATA
OUT
2)
4)
1
2
3
…
12
DATA
IN
2)
5)
1
2
3
…
12
FBA MAIN SW
FBA ACT1
FBA ACT2
Par. 01.01…99.99
FBA MAIN CW
Par. 10.01…99.99
1) See also other parameters which can be controlled from fieldbus.
2) The maximum number of data words used is protocol-dependent.
3) Profile/instance selection parameters. Fieldbus module specific parameters. For more
information, see the
User’s manual
of the appropriate fieldbus adapter module.
3)
3)
Parameter
table
1)
Fieldbus network
Fieldbus adapter
F
ie
ldbu
s-
sp
ec
ifi
c i
nter
fac
e
Profile
selection
Profile
selection
DATA OUT
selection
Group 53
DATA IN
selection
Group 52
FBA Profile
Start func
Cyclic communication
Acyclic communication
See the manual of the fieldbus
adapter module.
Summary of Contents for ACQ80
Page 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Page 2: ... Related documents are listed on page 13 ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Startup control with I O and ID run ...
Page 34: ...34 Using the control panel ...
Page 74: ...74 Program features ...
Page 78: ...78 Control macros ...
Page 380: ...380 Fieldbus control through a fieldbus adapter ...
Page 384: ...384 Parameterization with Drive Composer ...
Page 388: ...388 Parameterization with Automation builder drive manager ...