68 Program features
Miscellaneous
Backup and restore
You can make backups of the settings manually to the assistant control panel.
The assistant control panel also keeps one automatic backup. You can restore a
backup to another drive, or a new drive replacing a faulty one. You can make
backups and restore on the control panel or with the Drive composer PC tool.
Backup
Manual backup
Make a backup when necessary, for example, after you have started up the drive
or when you want to copy the settings to another drive.
Parameter changes from fieldbus interfaces are ignored unless you have forced
parameter saving with parameter
Automatic backup
The control panel has a dedicated space for one automatic backup. An
automatic backup is created two hours after the last parameter change. After
completing the backup, the panel waits for 24 hours before checking for
additional parameter changes. If any changes exist, it creates a new backup
overwriting the previous one when two hours have passed after the latest
change.
Notes
:
• You cannot adjust the delay time or disable the automatic backup function.
• Parameter changes from fieldbus interfaces are ignored unless you have
forced parameter saving with parameter
Restore
The backups are shown on the panel.
• Automatic backup is marked with icon and
• Manual backup is marked with icon .
To restore a backup, select it and press
.
In the following display you can view
backup contents and restore all parameters or select a subset to be restored.
Note:
To restore a backup, the drive must be in Local control.
Settings
Menu - Backups
Parameter
(page
Summary of Contents for ACQ80
Page 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Page 2: ... Related documents are listed on page 13 ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Startup control with I O and ID run ...
Page 34: ...34 Using the control panel ...
Page 74: ...74 Program features ...
Page 78: ...78 Control macros ...
Page 380: ...380 Fieldbus control through a fieldbus adapter ...
Page 384: ...384 Parameterization with Drive Composer ...
Page 388: ...388 Parameterization with Automation builder drive manager ...