ACQ800-37 Hardware Manual
91
Installation checklist and start-up
Actual signals and parameters of the supply unit control program visible also in
the inverter control program
No.
Name/Value
Description
FbEq
Def.
09 ACTUAL SIGNALS
Signals from the supply unit (line-side converter).
09.12
LCU ACT SIGNAL 1
Line-side converter signal selected by par. 95.08 LCU PAR1 SEL.
1 = 1
106
09.13
LCU ACT SIGNAL 2
Line-side converter signal selected by par. 95.09 LCU PAR2 SEL.
1 = 1
110
95 HARDWARE SPECIF
Line-side converter references and actual signal selections.
95.06
LCU Q PW REF
Reactive power reference for the line-side converter i.e. the value
for par. 24.02 Q POWER REF2 in the IGBT Supply Control
Program.
Scaling example 1: 10000 equals to a value of 10000 of parameter
24.02 Q POWER REF2 and 100% of par. 24.01 Q POWER REF
(i.e. 100% of the converter nominal power given in par. 04.06
CONV NOM POWER) when par. 24.03 Q POWER REF2 SEL is
set to PERCENT.
Scaling example 2: Par. 24.03 Q POWER REF2 SEL is set to kVAr.
A value of 1000 of par. 95.06 equals to 1000 kVAr of par. 24.02 Q
POWER REF2. Value of par. 24.01 Q POWER REF is then 100 ·
(1000 kVAr divided by converter nominal power in kVAr)%.
Scaling example 3: Par. 24.03 Q POWER REF2 SEL is set to PHI.
A value of 10000 of par. 95.06 equals to a value of 100 deg of
parameter 24.02 Q POWER REF2 which is limited to 30 deg. The
value of par. 24.01 Q POWER REF will be determined
approximately according to the following equation where
P
is read
from actual signal 1.09 POWER:
0
-10000 ... +10000
Setting range.
1 = 1
95.07
LCU DC REF
DC voltage reference for line converter i.e. the value for parameter
23.01 DC VOLT REF.
0
0 … 1100
Setting range in volts.
1 = 1 V
95.08
LCU PAR1 SEL
Selects the line converter address from which actual signal 9.12
LCU ACT SIGNAL 1 is read.
106
0 … 10000
Parameter index.
1 = 1
95.09
LCU PAR2 SEL
Selects the line converter address from which actual signal 9.13
LCU ACT SIGNAL 2 is read.
110
0 … 10000
Parameter index.
1 = 1
30
cos
P
S
---
P
P
2
Q
2
+
-----------------------
=
=
30 deg
S
Q
P
Positive reference 30 deg denotes capacitive load.
Negative reference 30 deg denotes inductive load.
-10000
+10000
0
30 (deg)
3000
-3000
10
1000
-1000
-10
-30
0
Par. 95.01
Par. 24.02
Summary of Contents for ACQ800 Series
Page 1: ...Hardware Manual ACQ800 37 Drives 55 to 450 kW 75 to 550 hp ACQ800 ...
Page 4: ......
Page 12: ...12 ACQ800 37 Hardware Manual Safety instructions ...
Page 24: ...24 ACQ800 37 Hardware Manual About this manual ...
Page 52: ...52 ACQ800 37 Hardware Manual Mechanical installation ...
Page 78: ...78 ACQ800 37 Hardware Manual Electrical installation ...
Page 84: ...84 ACQ800 37 Hardware Manual Motor control and I O board RMIO ...
Page 92: ...92 ACQ800 37 Hardware Manual Installation checklist and start up ...
Page 106: ...106 ACQ800 37 Hardware Manual Maintenance 3 4 5 6 8 7b 7a ...
Page 107: ...ACQ800 37 Hardware Manual 107 Maintenance 9 10 11 View from back ...
Page 123: ...ACQ800 37 Hardware Manual 123 Technical data Declaration of Conformity ...
Page 124: ...124 ACQ800 37 Hardware Manual Technical data ...
Page 128: ...128 ACQ800 37 Hardware Manual Dimensions Frame R6 ...
Page 129: ...ACQ800 37 Hardware Manual 129 Dimensions Frame R6 continued ...
Page 130: ...130 ACQ800 37 Hardware Manual Dimensions Frame R7i ...
Page 131: ...ACQ800 37 Hardware Manual 131 Dimensions Frame R7i continued ...
Page 132: ...132 ACQ800 37 Hardware Manual Dimensions Frame R7i continued ...
Page 133: ...ACQ800 37 Hardware Manual 133 Dimensions Frame R7i continued ...
Page 134: ...134 ACQ800 37 Hardware Manual Dimensions Frame R8i ...
Page 135: ...ACQ800 37 Hardware Manual 135 Dimensions Frame R8i continued ...
Page 136: ...136 ACQ800 37 Hardware Manual Dimensions Frame R8i continued ...
Page 137: ...ACQ800 37 Hardware Manual 137 Dimensions Frame R8i continued ...