ACQ800-37 Hardware Manual
87
Installation checklist and start-up
Supply unit (line-side converter) program set-up
Parameters of the IGBT supply unit need not be set during the start-up
procedure, or in normal use. In case the parameters of the supply unit
need to be changed, switch the control panel (optional) to view the line-
side converter as described in section
.
Alternatively, a PC equipped with a programming tool (e.g.
DriveWindow) can be connected to channel CH3 of the inverter unit’s
RDCU.
Note:
An automatic Line-Side Identification routine is active by default
and it is repeated each time the line-side converter receives a start
command after the control board (RMIO) is powered. The identification
should be performed at least once during the start-up. After this it can be
disabled with parameter 99.08 AUTO LINE ID RUN, especially if a quick
start is needed. If the phase order is changed after the first start, the
Line-side Identification routine needs to be repeated.
Note:
It is recommended to set parameter 16.15 START MODE to
LEVEL
•
if the motor is started and stopped frequently. This prolongs the life of
the charging contactor,
•
if the drive is equipped with the emergency stop option,
•
when it is required to start the motor without delay after the start
command, or
•
if the drive is connected to a common DC bus. Otherwise the
charging resistors may be damaged.
Note:
The output voltage of the drive can be raised using a parameter
setting; for example, it is possible to run a 500 V motor off a 400 V
supply. Contact your local ABB representative for more information.
Inverter control program set-up
Follow the instructions in the
Firmware Manual
of the inverter unit to start
up the drive and to set the drive parameters.
See the
Firmware Manual
of the
inverter unit.
On-load checks
Check that the cooling fans rotate freely in the right direction, and the air
flows upwards.
Check visually that the fans rotate in
the direction indicated by an arrow
on the fan housing.
Check the direction of rotation of the motor.
Action
Additional information
Summary of Contents for ACQ800 Series
Page 1: ...Hardware Manual ACQ800 37 Drives 55 to 450 kW 75 to 550 hp ACQ800 ...
Page 4: ......
Page 12: ...12 ACQ800 37 Hardware Manual Safety instructions ...
Page 24: ...24 ACQ800 37 Hardware Manual About this manual ...
Page 52: ...52 ACQ800 37 Hardware Manual Mechanical installation ...
Page 78: ...78 ACQ800 37 Hardware Manual Electrical installation ...
Page 84: ...84 ACQ800 37 Hardware Manual Motor control and I O board RMIO ...
Page 92: ...92 ACQ800 37 Hardware Manual Installation checklist and start up ...
Page 106: ...106 ACQ800 37 Hardware Manual Maintenance 3 4 5 6 8 7b 7a ...
Page 107: ...ACQ800 37 Hardware Manual 107 Maintenance 9 10 11 View from back ...
Page 123: ...ACQ800 37 Hardware Manual 123 Technical data Declaration of Conformity ...
Page 124: ...124 ACQ800 37 Hardware Manual Technical data ...
Page 128: ...128 ACQ800 37 Hardware Manual Dimensions Frame R6 ...
Page 129: ...ACQ800 37 Hardware Manual 129 Dimensions Frame R6 continued ...
Page 130: ...130 ACQ800 37 Hardware Manual Dimensions Frame R7i ...
Page 131: ...ACQ800 37 Hardware Manual 131 Dimensions Frame R7i continued ...
Page 132: ...132 ACQ800 37 Hardware Manual Dimensions Frame R7i continued ...
Page 133: ...ACQ800 37 Hardware Manual 133 Dimensions Frame R7i continued ...
Page 134: ...134 ACQ800 37 Hardware Manual Dimensions Frame R8i ...
Page 135: ...ACQ800 37 Hardware Manual 135 Dimensions Frame R8i continued ...
Page 136: ...136 ACQ800 37 Hardware Manual Dimensions Frame R8i continued ...
Page 137: ...ACQ800 37 Hardware Manual 137 Dimensions Frame R8i continued ...