ACS 160 User’s Manual
19
Q Type Series and Technical Data
* 180 % of nominal current I
2N
**150 % of nominal current I
2N
***
No overloadability!
Derate to 90 % when using 8 kHz switching frequency. Rating is not valid if the ACS 160 is installed on top of
a non ABB motor.
****
Follow local rules for cable cross-sections. Shielded motor cable is recommended when mounting the ACS 160 on the wall.
***** Fuse type: UL class CC or T. For non-UL installations IEC269gG.
ACS 160 is suitable for use in a circuit capable of delivering not more than 65 kA rms symmetrical amperes, 500 V.
Note!
Use 75
°
C (167
°
F) rated power cable.
Motor Mounted
Wall Mounted
Filterless
3~ Input U
1
380-500 V
±10 %
ACS 163-
1K1-
3-A/R
1K6-
3-A/R
2K1-
3-A/R
2K7-
3-A
4K1-
3-A/R
1K1-
3-D/U
1K6-
3-D/U
2K1-
3-D/U
2K7-
3-D
4K1-
3-D/U
Built-in filter
3~ Input U
1
380-480 V
±10 %
ACS 163-
1K1-
3-B/S
1K6-
3-B/S
2K1-
3-B/S
2K7-
3-B
4K1-
3-B/S
1K1-
3-E/V
1K6-
3-E/V
2K1-
3-E/V
2K7-
3-E
4K1-
3-E/V
Frame Size
R1
R2
R1
R2
Nominal ratings
(See
Nominal motor P
N
kW /
Hp
0.55 /
0.74
0.75 /
1
1.1 /
1.5
1.5
2.2 /
3
0.55 /
0.74
0.75 /
1
1.1 /
1.5
1.5
2.2 /
3
Input current I
1N
A
1.6
2.2
3.2
4.1
6.0
1.6
2.2
3.2
4.1
6.0
Continuous output
current I
2N
A
1.8
2.4
3.4
4.1
5.4
1.8
2.4
3.4
4.1
5.4
Max. current I
max
*
A
2.7
3.6
5.1
6.2
8.1
2.7
3.6
5.1
6.2
8.1
Max. starting
current **
A
3.2
4.3
6.1
7.4
9.7
3.2
4.3
6.1
7.4
9.7
Continuous output
current squared
torque I
2NSQ
***
A
2.2
2.8
3.8
5.0
6.6
2.2
2.8
3.8
5.0
6.6
Output voltage U
2
V
0 - U
1
Switching
frequency f
SW
kHz
4 (Standard)
8 (Low noise)
Protection limits
(See
Overcurrent (peak)
A
7.1
9.5
13
16
21
7.1
9.5
13
16
21
Overvoltage:
Trip limit
V DC
875
Undervoltage:
Trip limit
V DC
333
Overtemperature
°
C / (
°
F)
105 (221) (inside power module)
Max. wire sizes and screw torque of connectors
Power terminals
****
mm
2
single core: 4 (AWG 12), stranded: 2.5 (AWG 14) / torque 0.8 Nm
Control terminals
mm
2
0.5 - 1.5 (AWG22...AWG16) / torque 0.4 Nm
Line fuse 3~ *****
ACS163-
A
4
4
6
10
10
4
4
6
10
10
Power losses
(at nominal point)
Power circuit
W
17
23
33
45
66
17
23
33
45
66
Control circuit
W
16
17
18
19
20
18
19
20
21
22
Maximum cable lengths can be found in section EMC Instructions and Maximum Cable Lengths
Summary of Contents for ACS 160
Page 2: ......
Page 4: ......
Page 10: ...viii ACS 160 User s Manual ...
Page 12: ...2 ACS 160 User s Manual ...
Page 32: ...22 ACS 160 User s Manual ...
Page 42: ...32 ACS 160 User s Manual ...
Page 56: ...46 ACS 160 User s Manual ...
Page 116: ...106 ACS 160 User s Manual ...
Page 122: ...112 ACS 160 User s Manual ...
Page 126: ...116 ACS 160 User s Manual ...
Page 136: ...126 ACS 160 User s Manual ...
Page 137: ......