Group 25: Critical Freq
In some mechanical systems, certain speed ranges can cause resonance problems. With this
parameter group, it is possible to set up to two different speed ranges that the ACS 160 will skip over.
Example
: A fan system vibrates badly from 18 Hz to 23 Hz and from 46 Hz to 52 Hz. Set the
parameters as follows:
CRIT
FREQ
1
LO
= 18 Hz and
CRIT
FREQ
1
HI
= 23 Hz
CRIT
FREQ
2
LO
= 46 Hz and
CRIT
FREQ
2
HI
= 52 Hz
Figure 11 Example of critical frequencies setting in a fan system with bad vibrations at frequency
ranges 18 Hz to 23 Hz and 46 Hz to 52 Hz.
Code Description
2501
CRIT FREQ SEL
Critical frequencies activation.
0 =
OFF
1 =
ON
2502
CRIT FREQ 1 LO
Critical frequency 1 start.
Note!
If LOW > HI, no critical frequency lock-out will happen.
2503
CRIT FREQ 1 HI
Critical frequency 1 end.
2504
CRIT FREQ 2 LO
Critical frequency 2 start.
2505
CRIT FREQ 2 HI
Critical frequency 2 end.
Note!
If LOW > HI, no critical frequency lock-out will happen.
f
output
52
46
23
18
f
REF
(Hz)
f1L
18
f2L
46
f1H
23
f2H
52
Summary of Contents for ACS 160
Page 2: ......
Page 4: ......
Page 10: ...viii ACS 160 User s Manual ...
Page 12: ...2 ACS 160 User s Manual ...
Page 32: ...22 ACS 160 User s Manual ...
Page 42: ...32 ACS 160 User s Manual ...
Page 56: ...46 ACS 160 User s Manual ...
Page 116: ...106 ACS 160 User s Manual ...
Page 122: ...112 ACS 160 User s Manual ...
Page 126: ...116 ACS 160 User s Manual ...
Page 136: ...126 ACS 160 User s Manual ...
Page 137: ......