82
ACS 160 User’s Manual
Group 32: Supervision
Parameters of this group are used together with relay output parameters 1401
RELAY
OUTPUT
1 and
1402
RELAY
OUTPUT
2. Any two parameters of the Operating Data group (Group 1) can be
supervised. Relays can be configured to be energised when the values of supervised parameters are
either too low or too high.
Code Description
3201
SUPERV 1 PARAM
First supervised parameter number of the Operating Data group (Group 01).
3202
SUPERV 1 LIM LO
First supervision limit low. Display of this parameter depends on selected supervised parameter (3201).
3203
SUPERV 1 LIM HI
First supervision limit high. Display of this parameter depends on selected supervised parameter (3201).
3204
SUPERV 2 PARAM
Second supervised parameter number of the Operating Data group (Group 01).
3205
SUPERV 2 LIM LO
Second supervision limit low. Display of this parameter depends on selected supervised parameter (3204).
3206
SUPERV 2 LIM HI
Second supervision limit high. Display of this parameter depends on selected supervised parameter (3204).