ACS 160 User’s Manual
89
4007
ACT1 INPUT SEL
Source for actual value 1 (
ACT
1).
1 = AI 1
Analogue input 1 is used as actual value 1.
2 = AI 2
Analogue input 2 is used as actual value 1.
4008
ACT2 INPUT SEL
Source for actual value 2 (
ACT
2).
1 = AI 1
Analogue input 1 is used as actual value 2.
2 = AI 2
Analogue input 2 is used as actual value 2.
4009
ACT1 MINIMUM
Minimum value for actual value 1 (
ACT
1). Refer to Figure 22 and to Group 13 parameters for analogue input
minimum and maximum settings.
4010
ACT1 MAXIMUM
Maximum value for actual value 1 (
ACT
1). Refer to Figure 22 and to Group 13 parameters for analogue
input minimum and maximum settings.
4011
ACT2 MINIMUM
Minimum value for actual value 2 (
ACT
2). Refer to parameter 4009.
4012
ACT2 MAXIMUM
Maximum value for actual value 2 (
ACT
2). Refer to parameter 4010.
Figure 22 Actual value scaling. The range of the analogue input signal is set by parameters 1301
and 1302 or parameters 1304 and 1305, depending on the analogue input used.
Code Description
ACT
1 (%)
Analogue input signal
ACT
1
MINIMUM
AI min
AI max
A
CT
1 (%)
Analogue input signal
ACT
1
MINIMUM
ACT
1
MAXIMUM
AI min
AI max
ACT
1
MAXIMUM
Summary of Contents for ACS 160
Page 2: ......
Page 4: ......
Page 10: ...viii ACS 160 User s Manual ...
Page 12: ...2 ACS 160 User s Manual ...
Page 32: ...22 ACS 160 User s Manual ...
Page 42: ...32 ACS 160 User s Manual ...
Page 56: ...46 ACS 160 User s Manual ...
Page 116: ...106 ACS 160 User s Manual ...
Page 122: ...112 ACS 160 User s Manual ...
Page 126: ...116 ACS 160 User s Manual ...
Page 136: ...126 ACS 160 User s Manual ...
Page 137: ......