ACS 300 User’s Manual
47
Chapter 7 - Drive Parameters
Note! The factory setting for display language is English, refer to
Page 1 parameter LANGUAGE for display language selection.
Parameters marked with (0) can only be altered with the
ACS 300 stopped otherwise START IS ACTIVE message is
displayed. (L) indicates that the parameter can be altered in Local
control mode only.
Table 7-1 Drive parameters and their factory settings.
Code
Parameter
Range
Default
Cus
tomer
Page
Description
PAGE 1 (*P2)
Display only
-
-
51
Press
to change to
page 2
101
OUTPUT f
Display only
–
–
51
Frequency to motor
102
REF FREQ/
LOC FREQ (L)
f
MIN
– f
MAX
0 Hz
51
Frequency reference from
remote or control panel
103
SPEED
Display only
–
–
51
Calculated motor speed
104
OUTPUT I
Display only
–
–
52
Motor current
105
COPY
Exit/Read/Write/
Set Factory Def.
Exit
–
52
Transfers all settings to and
from panel
106
MIN FREQ
0.0 – 200/500 Hz
1)
0.0 Hz
52
Reference input minimum
frequency
107
MAX FREQ
0.0 – 200/500 Hz
1)
50 Hz
52
Maximum output frequency
108
ACC 1
0.1 – 1800 s
3 s
52
Time for Ref Min f - Ref Max f
acceleration ramp
109
DEC 1
0.1 – 1800 s
3 s
52
Time for Ref Max f - Ref Min f
deceleration ramp
110
ACC 2
0.1 – 1800 s
3 s
52
Time for Ref Min f - Ref Max f
acceleration ramp
Summary of Contents for ACS 300
Page 14: ...xiv ACS 300 User s Manual Table of Contents ...
Page 24: ...10 ACS 300 User s Manual Chapter 1 Overview of This Manual ...
Page 28: ...14 ACS 300 User s Manual Chapter 2 Mechanical Installation ...
Page 50: ...36 ACS 300 User s Manual Chapter 4 Control Connections ...
Page 60: ...46 ACS 300 User s Manual Chapter 6 Control and Parameter Logic ...