ACS 300 User’s Manual
85
Chapter 9 - Technical Data
Auxiliary
voltage
+24 V DC
±
15%
max. 50 mA
One analogue
output
Current output
0 (4) to 20 mA
R
L
<500
Ω
Source (selected by
parameter)
Output
frequency
scaled 0 to maximum
frequency
Output (motor)
current
scaled 0 to 1.5 x I
N
Output frequency
reference
scaled 0 to maximum
frequency
Accuracy
Frequency out-
puts
±
2 %
Motor current out-
put
±
10 %
Ripple
1 %
Response time
50 ms
Five digital
inputs
Refer to Chapter 4, on
page 27 for a descrip-
tion of the functions of
the digital inputs
Max input 48 V
10k
Ω
<Z
IN
<30k
Ω
V
IN
low < 3V
V
IN
high > 10 V
Two relay
outputs
Programmable, refer to Chapter 7 Page 2 parameters 225 and
226
Max switching
voltage
250 V AC/ 150 V DC
Max switching
current
8 A 250 V AC /24 V DC
Max switching
power
2000 VA / 250 V AC
192 W / 24 V DC
Max continuous
current
2 A rms
Control earthing
Frame earth
default setting
see page 23
Floating
alternate
see page 23