ACS 400 User’s Manual
117
Group 52: Standard Modbus
The ACS 400 can be connected to Modbus fieldbus system. Parameters of this group are used to
set up station number, communication speed and parity. Parameters 5206 - 5215 are diagnostic
counters that can be used to debug the fieldbus system. Refer to “Standard Serial Communication”
on page 129 for more information.
Modifications of parameters in this group take effect on the next power-up.
Code Description
5201
STATION NUMBER
Sets the slave number for the ACS 400 in Modbus network.
Range: 1 - 247
5202
COMM SPEED
Defines the communication speed of the ACS 400 in bits per second (bits/s).
5203
PARITY
Defines the parity to be used with the Modbus communication. Parameter also defines the number of stop
bits. With Modbus communication, the number of stop bits is 2 with no parity bit, and 1 with even or odd
parity.
0 =
NONE
1 =
EVEN
2 =
ODD
5206
BAD MESSAGES
This diagnostics counter increases by one every time the ACS 400 finds any kind of communication error.
During normal operation, this counter rarely increases.
5207
GOOD MESSAGES
This diagnostics counter increases by one every time a valid Modbus message has been received by the
ACS 400. During normal operation, this counter is increasing constantly.
5208
BUFFER OVERRUNS
Longest possible message length for the ACS 400 is 32 bytes. If a message exceeding 32 bytes is received,
this diagnostic counter increases by one every time a character which cannot be placed in the buffer is
received.
5209
FRAME ERRORS
This diagnostic counter increases by one every time a character with a framing error is received from the
bus.
• Communication speed settings of the devices connected in the bus differ.
• Ambient noise levels may be too high.
5210
PARITY ERRORS
This diagnostic counter increases by one every time a character with a parity error is received from the bus.
• Parity settings of the devices connected on the bus differ.
• Ambient noise levels may be too high.
3 = 300 bits/s
48 = 4800 bits/s
6 = 600 bits/s
96 = 9600 bits/s
12 = 1200 bits/s
192 = 19200 bits/s
24 = 2400 bits/s
http://nicontrols.com
Summary of Contents for ACS 400
Page 3: ...http nicontrols com ...
Page 5: ...http nicontrols com ...
Page 7: ...iv ACS 400 User s Manual http nicontrols com ...
Page 45: ...34 ACS 400 User s Manual http nicontrols com ...
Page 52: ...ACS 400 User s Manual 41 Motor Will Not Run http nicontrols com ...
Page 53: ...42 ACS 400 User s Manual Motor Stalls during Acceleration http nicontrols com ...
Page 54: ...ACS 400 User s Manual 43 Overvoltage Fault Indication http nicontrols com ...
Page 55: ...44 ACS 400 User s Manual Overcurrent Fault Indication http nicontrols com ...
Page 56: ...ACS 400 User s Manual 45 Overload Fault Indication http nicontrols com ...
Page 57: ...46 ACS 400 User s Manual Undervoltage Fault Indication http nicontrols com ...
Page 58: ...ACS 400 User s Manual 47 External Fault Indication http nicontrols com ...
Page 59: ...48 ACS 400 User s Manual No Operator Display http nicontrols com ...
Page 75: ...64 ACS 400 User s Manual http nicontrols com ...
Page 161: ...150 ACS 400 User s Manual http nicontrols com ...
Page 167: ...156 ACS 400 User s Manual http nicontrols com ...
Page 177: ...166 ACS 400 User s Manual http nicontrols com ...
Page 179: ...168 ACS 400 User s Manual ACS 400 NEMA Type 1 Enclosure R2 Frame Size http nicontrols com ...
Page 180: ...ACS 400 User s Manual 169 ACS 400 NEMA Type 1 Enclosure R3 Frame Size http nicontrols com ...
Page 181: ...170 ACS 400 User s Manual ACS 400 NEMA Type 1 Enclosure R4 Frame Size http nicontrols com ...
Page 182: ...ACS 400 User s Manual 171 ACS 400 NEMA Type 12 4 Enclosure R1 Frame Size http nicontrols com ...
Page 183: ...172 ACS 400 User s Manual ACS 400 NEMA 12 4 Enclosure R2 Frame Size http nicontrols com ...
Page 184: ...ACS 400 User s Manual 173 ACS 400 NEMA Type 12 4 R3 Frame Size http nicontrols com ...
Page 185: ...174 ACS 400 User s Manual ACS 400 NEMA Type 12 4 R4 Frame Size http nicontrols com ...
Page 186: ...http nicontrols com ...