ACS 400 User’s Manual
19
Q Protection Features
The ACS 400 has a number of protective features:
The ACS 400 has the following LED alarm and fault indicators:
•
For location of LEDs, see section E or, if an ACS-PAN-A control panel is connected, see
“Programming” on page 25.
Note! Whenever the ACS 400 detects a fault condition, the fault relay activates. The motor
stops and the ACS 400 will wait to be reset. If the fault still persists and no external
cause has been identified, contact your local ABB sales or service office.
• Overcurrent
• Overvoltage
• Undervoltage
• Overtemperature
• Output ground fault
• Output short circuit
• Input phase loss (3~)
• I/O terminal short circuit protection
• Motor overload protection (see Section R)
• Output overload protection (see Section S)
• Stall protection
• Underload
Red LED: off
Green LED: blinking
ABNORMAL CONDITION
ABNORMAL CONDITION:
• ACS 400 cannot fully follow control
commands.
• Blinking lasts 15 seconds.
POSSIBLE CAUSES:
• Acceleration or deceleration ramp is
too fast in relation to load torque
requirement
• A momentary power interruption
Red LED: on
Green LED: on
FAULT
ACTION:
• Apply a stop signal to reset fault.
• Apply a start signal to restart the drive.
NOTE:
If the drive fails to start, check that the
input voltage is within the tolerance range.
POSSIBLE CAUSES:
• Transient overcurrent
• Over-/undervoltage
• Overtemperature
CHECK:
• the supply line for disturbances.
• the drive for mechanical problems that
might cause overcurrent.
• that the heat sink is clean.
Red LED: blinking
Green LED: on
FAULT
ACTION:
• Turn the power off.
• Wait for the LED’s to turn off.
• Turn the power back on.
Caution! This action may start the drive.
POSSIBLE CAUSE:
• Output ground fault
• Short circuit
• DC bus ripple too large
CHECK:
• the insulation in the motor circuit.
http://nicontrols.com
Summary of Contents for ACS 400
Page 3: ...http nicontrols com ...
Page 5: ...http nicontrols com ...
Page 7: ...iv ACS 400 User s Manual http nicontrols com ...
Page 45: ...34 ACS 400 User s Manual http nicontrols com ...
Page 52: ...ACS 400 User s Manual 41 Motor Will Not Run http nicontrols com ...
Page 53: ...42 ACS 400 User s Manual Motor Stalls during Acceleration http nicontrols com ...
Page 54: ...ACS 400 User s Manual 43 Overvoltage Fault Indication http nicontrols com ...
Page 55: ...44 ACS 400 User s Manual Overcurrent Fault Indication http nicontrols com ...
Page 56: ...ACS 400 User s Manual 45 Overload Fault Indication http nicontrols com ...
Page 57: ...46 ACS 400 User s Manual Undervoltage Fault Indication http nicontrols com ...
Page 58: ...ACS 400 User s Manual 47 External Fault Indication http nicontrols com ...
Page 59: ...48 ACS 400 User s Manual No Operator Display http nicontrols com ...
Page 75: ...64 ACS 400 User s Manual http nicontrols com ...
Page 161: ...150 ACS 400 User s Manual http nicontrols com ...
Page 167: ...156 ACS 400 User s Manual http nicontrols com ...
Page 177: ...166 ACS 400 User s Manual http nicontrols com ...
Page 179: ...168 ACS 400 User s Manual ACS 400 NEMA Type 1 Enclosure R2 Frame Size http nicontrols com ...
Page 180: ...ACS 400 User s Manual 169 ACS 400 NEMA Type 1 Enclosure R3 Frame Size http nicontrols com ...
Page 181: ...170 ACS 400 User s Manual ACS 400 NEMA Type 1 Enclosure R4 Frame Size http nicontrols com ...
Page 182: ...ACS 400 User s Manual 171 ACS 400 NEMA Type 12 4 Enclosure R1 Frame Size http nicontrols com ...
Page 183: ...172 ACS 400 User s Manual ACS 400 NEMA 12 4 Enclosure R2 Frame Size http nicontrols com ...
Page 184: ...ACS 400 User s Manual 173 ACS 400 NEMA Type 12 4 R3 Frame Size http nicontrols com ...
Page 185: ...174 ACS 400 User s Manual ACS 400 NEMA Type 12 4 R4 Frame Size http nicontrols com ...
Page 186: ...http nicontrols com ...