22
ACS 400 User’s Manual
400V Series
3~Input 380 - 480V
+/- 10% 50/60Hz
ACS401x
0043x
0053x
0063x
0093x
0113x
0163x
0203x
0253x
0303x
0413x
Frame Size
Unit
R1
R2
R3
R4
Nominal Ratings (See G)
Nominal Motor P
N
Normal Duty
Hp
3.0
5.0
7.5
10
15
20
25
30
40
50
Input Current I
1NND
A
6.2
8.3
11.1
14.8
21.5
29.0
35.0
41.0
56.0
68.0
Output Current I
2NND
A
6.6
8.8
11.6
15.3
23.0
30.0
38.0
44.0
59.0
72.0
Max. Output Current
I
2NNDmax
*
A
7.3
9.7
12.8
16.8
25.3
33
42
48
65
79
Nominal Motor P
N
Heavy Duty
kW
Hp
2.0
3.0
5.0
7.5
10
15
20
25
30
40
Input current I
1N
A
4.7
6.2
8.3
11.1
14.8
21.5
29
35
41
56
Output Current I
2N
A
4.9
6.6
7.7
11.6
15.3
23
30
38
44
59
Max. Output current
I
2Nmax
*
A
7.4
9.9
13.2
17.4
23
34
45
57
66
88
Output Voltage V
2
V
0 - V
1
Switching Frequency
kHz
4 (Standard)
8 (Low Noise**)
Protection Limits
Overcurrent (peak)
A
20.3
27.5
37
48
64
76
99
125
145
195
Overvoltage:
Running
Start Inhibit
VDC
VDC
842 (corresponds to 624 VAC input)
661 (in input voltage range 380-415 VAC)
765 (in input voltage range 440-480 VAC)
Undervoltage:
Running
Start Inhibit
VDC
VDC
333 (corresponds to 247 VAC input)
436 (in input voltage range 380-415 VAC)
505 (in input voltage range 440-480 VAC)
Overtemperature
°
C /
°F
95
° C / 203° F
(Heat Sink)
Max. Cable Length
f
SW
=4kHz****
m / ft.
100 / 320’
200 / 640’
200 / 640’
200 / 640’
Max. wire sizes and screw torque of connectors
Power terminals
***
mm
2
/ Nm
/ lb/in.
10, AWG6 (stranded) /
Torque 1.3-1.5 Nm / 11 - 13 lb/in.
16, AWG4
(stranded) /
Torque
1.5-1.8 Nm /
13 - 16 lb/in.
35, AWG2 (stranded) /
Torque 3.2-3.7 Nm / 28
- 32 lb/in.
Control terminals
mm
2
0.5 - 1.5 (AWG22...AWG16) / Torque 0.4 Nm
Line fuse 3~
****
A
10
15
15
20
30
40
50
60
80
100
Bussman Fuse Type
KTK-10 KTK-15 KTK-15 KTK-20 KTK-30 JJS-40
JJS-50
JJS-60
JJS-80
JJS-100
Power losses
Power circuit
W
90
120
170
230
330
450
560
660
900
1100
Control circuit
W
6
6
6
6
6
6
6
6
6
6
http://nicontrols.com
Summary of Contents for ACS 400
Page 3: ...http nicontrols com ...
Page 5: ...http nicontrols com ...
Page 7: ...iv ACS 400 User s Manual http nicontrols com ...
Page 45: ...34 ACS 400 User s Manual http nicontrols com ...
Page 52: ...ACS 400 User s Manual 41 Motor Will Not Run http nicontrols com ...
Page 53: ...42 ACS 400 User s Manual Motor Stalls during Acceleration http nicontrols com ...
Page 54: ...ACS 400 User s Manual 43 Overvoltage Fault Indication http nicontrols com ...
Page 55: ...44 ACS 400 User s Manual Overcurrent Fault Indication http nicontrols com ...
Page 56: ...ACS 400 User s Manual 45 Overload Fault Indication http nicontrols com ...
Page 57: ...46 ACS 400 User s Manual Undervoltage Fault Indication http nicontrols com ...
Page 58: ...ACS 400 User s Manual 47 External Fault Indication http nicontrols com ...
Page 59: ...48 ACS 400 User s Manual No Operator Display http nicontrols com ...
Page 75: ...64 ACS 400 User s Manual http nicontrols com ...
Page 161: ...150 ACS 400 User s Manual http nicontrols com ...
Page 167: ...156 ACS 400 User s Manual http nicontrols com ...
Page 177: ...166 ACS 400 User s Manual http nicontrols com ...
Page 179: ...168 ACS 400 User s Manual ACS 400 NEMA Type 1 Enclosure R2 Frame Size http nicontrols com ...
Page 180: ...ACS 400 User s Manual 169 ACS 400 NEMA Type 1 Enclosure R3 Frame Size http nicontrols com ...
Page 181: ...170 ACS 400 User s Manual ACS 400 NEMA Type 1 Enclosure R4 Frame Size http nicontrols com ...
Page 182: ...ACS 400 User s Manual 171 ACS 400 NEMA Type 12 4 Enclosure R1 Frame Size http nicontrols com ...
Page 183: ...172 ACS 400 User s Manual ACS 400 NEMA 12 4 Enclosure R2 Frame Size http nicontrols com ...
Page 184: ...ACS 400 User s Manual 173 ACS 400 NEMA Type 12 4 R3 Frame Size http nicontrols com ...
Page 185: ...174 ACS 400 User s Manual ACS 400 NEMA Type 12 4 R4 Frame Size http nicontrols com ...
Page 186: ...http nicontrols com ...