ACS 400 User’s Manual
81
Group 12: Constant Speeds
The ACS 400 has 7 programmable constant speeds, ranging from 0 to 250 Hz. Negative speed
values cannot be given for constant speeds.
Constant speed selections are ignored if the process PID reference is followed, the drive is in local
control mode or PFC (Pump-Fan Control) is active.
Note! Parameter 1208
CONST
SPEED
7 also acts as a so-called fault speed which may be activated
if the control signal is lost. Refer to parameter 3001
AI
<
MIN
FUNCTION
and parameter 3002
PANEL
LOSS
.
Code Description
1201
CONST SPEED SEL
This parameter defines which digital inputs are used to select Constant Speeds.
0 =
NOT
SEL
Constant speed function disabled.
1...5 = DI1...DI5
Constant Speed 1 is selected with digital inputs DI1-DI5. Digital input activated = Constant Speed 1
activated.
6 = DI1,2
Three Constant Speeds (1 ... 3) are selected with two digital inputs.
Constant Speed selection with digital inputs DI1, 2.
Table 8 Constant Speed selection with digital inputs DI1, 2.
0 = DI deactivated, 1 = DI activated
7 = DI3,4
Three Constant Speeds (1 ... 3) are selected with two digital inputs as in DI1, 2.
8 = DI4,5
Three Constant Speeds (1 ... 3) are selected with two digital inputs as in DI1, 2.
9 = DI1,2,3
Seven Constant Speeds (1 ... 7) are selected with three digital inputs.
Table 9 Constant Speed selection with digital inputs DI1, 2, 3.
0 = DI deactivated, 1 = DI activated
10 = DI3,4,5
Seven Constant Speeds (1 ... 7) are selected with three digital inputs as in DI1, 2, 3.
1202
-1208
CONST SPEED 1... CONST SPEED 7
Constant speeds 1-7.
DI 1
DI 2
Function
0
0
No constant speed
1
0
Constant speed 1 (1202)
0
1
Constant speed 2 (1203)
1
1
Constant speed 3 (1204)
DI 1
DI 2
DI 3
Function
0
0
0
No constant speed
1
0
0
Constant speed 1 (1202)
0
1
0
Constant speed 2 (1203)
1
1
0
Constant speed 3 (1204)
0
0
1
Constant speed 4 (1205)
1
0
1
Constant speed 5 (1206)
0
1
1
Constant speed 6 (1207)
1
1
1
Constant speed 7 (1208)
http://nicontrols.com
Summary of Contents for ACS 400
Page 3: ...http nicontrols com ...
Page 5: ...http nicontrols com ...
Page 7: ...iv ACS 400 User s Manual http nicontrols com ...
Page 45: ...34 ACS 400 User s Manual http nicontrols com ...
Page 52: ...ACS 400 User s Manual 41 Motor Will Not Run http nicontrols com ...
Page 53: ...42 ACS 400 User s Manual Motor Stalls during Acceleration http nicontrols com ...
Page 54: ...ACS 400 User s Manual 43 Overvoltage Fault Indication http nicontrols com ...
Page 55: ...44 ACS 400 User s Manual Overcurrent Fault Indication http nicontrols com ...
Page 56: ...ACS 400 User s Manual 45 Overload Fault Indication http nicontrols com ...
Page 57: ...46 ACS 400 User s Manual Undervoltage Fault Indication http nicontrols com ...
Page 58: ...ACS 400 User s Manual 47 External Fault Indication http nicontrols com ...
Page 59: ...48 ACS 400 User s Manual No Operator Display http nicontrols com ...
Page 75: ...64 ACS 400 User s Manual http nicontrols com ...
Page 161: ...150 ACS 400 User s Manual http nicontrols com ...
Page 167: ...156 ACS 400 User s Manual http nicontrols com ...
Page 177: ...166 ACS 400 User s Manual http nicontrols com ...
Page 179: ...168 ACS 400 User s Manual ACS 400 NEMA Type 1 Enclosure R2 Frame Size http nicontrols com ...
Page 180: ...ACS 400 User s Manual 169 ACS 400 NEMA Type 1 Enclosure R3 Frame Size http nicontrols com ...
Page 181: ...170 ACS 400 User s Manual ACS 400 NEMA Type 1 Enclosure R4 Frame Size http nicontrols com ...
Page 182: ...ACS 400 User s Manual 171 ACS 400 NEMA Type 12 4 Enclosure R1 Frame Size http nicontrols com ...
Page 183: ...172 ACS 400 User s Manual ACS 400 NEMA 12 4 Enclosure R2 Frame Size http nicontrols com ...
Page 184: ...ACS 400 User s Manual 173 ACS 400 NEMA Type 12 4 R3 Frame Size http nicontrols com ...
Page 185: ...174 ACS 400 User s Manual ACS 400 NEMA Type 12 4 R4 Frame Size http nicontrols com ...
Page 186: ...http nicontrols com ...