ACS 400 User’s Manual
57
Application Macro 3-wire
This macro is intended for those applications where the drive is controlled using momentary push-
buttons. It gives two more preset speeds compared to Factory Macro (1) by using DI4 and DI5.
The value of parameter 9902 is 2 (3-
WIRE
).
*Constant speed selection: 0 = open, 1 = connected
Note! Stop input (
DI
2) deactivated: panel START/STOP button interlocked (local).
Application Macro 3-wire parameter values:
Input signals
Output signals
Jumper Setting
• Start, stop and direction
(DI1,2,3)
• An. output AO: Frequency
• Analog reference (AI1)
• Relay output 1: Fault
• Preset speed selection (DI4,5)
• Relay output 2: Running
DI4
DI5
Output
0
0
Reference through AI1
1
0
Constant speed 1 (1202)
0
1
Constant speed 2 (1203)
1
1
Constant speed 3 (1204)
1001
EXT
1
COMMANDS
4 (
DI
1
P
,2
P
,3)
1402
RELAY
OUTPUT
2
2 (
RUN
)
1002
EXT
2
COMMANDS
0 (
NOT
SEL
)
1503
AO
CONTENT
MAX
60 Hz
1003
DIRECTION
3 (
REQUEST
)
1601
RUN
ENABLE
0 (
NOT
SEL
)
1102
EXT
1/
EXT
2
SEL
6 (
EXT
1)
1604
FAULT
RESET
SEL
0 (
KEYPAD
)
1103
EXT
REF
1
SELECT
1 (
AI
1)
2008
MAXIMUM
FREQ
60 Hz
1105
EXT
REF
1
MAX
60 Hz
2105
PREMAGN
SEL
0 (
NOT
SEL
)
1106
EXT
REF
2
SELECT
0 (
KEYPAD
)
2201
ACC
/
DEC
1/2
SEL
0 (
NOT
SEL
)
1201
CONST
SPEED
SEL
8 (
DI
4,5)
4001
PID
GAIN
1.0
1401
RELAY
OUTPUT
1
3 (
FAULT
(-1))
4002
PID
INTEG
TIME
60 s
External Reference 1: 0...10 V <=> 0...50 Hz
Reference voltage 10 VDC
Not used
Output frequency 0...20 mA <=> 0...50 Hz
+24 VDC
Momentary activation with DI2 activated: Start
Momentary deactivation: Stop
Activate to reverse rotation: Fwd/Rev
Constant speed selection*
Constant speed selection*
Relay output 1, programmable
Default operation: fault => 17 connected to 18
Relay output 2, programmable
Default operation: running => 20 connected to 22
http://nicontrols.com
Summary of Contents for ACS 400
Page 3: ...http nicontrols com ...
Page 5: ...http nicontrols com ...
Page 7: ...iv ACS 400 User s Manual http nicontrols com ...
Page 45: ...34 ACS 400 User s Manual http nicontrols com ...
Page 52: ...ACS 400 User s Manual 41 Motor Will Not Run http nicontrols com ...
Page 53: ...42 ACS 400 User s Manual Motor Stalls during Acceleration http nicontrols com ...
Page 54: ...ACS 400 User s Manual 43 Overvoltage Fault Indication http nicontrols com ...
Page 55: ...44 ACS 400 User s Manual Overcurrent Fault Indication http nicontrols com ...
Page 56: ...ACS 400 User s Manual 45 Overload Fault Indication http nicontrols com ...
Page 57: ...46 ACS 400 User s Manual Undervoltage Fault Indication http nicontrols com ...
Page 58: ...ACS 400 User s Manual 47 External Fault Indication http nicontrols com ...
Page 59: ...48 ACS 400 User s Manual No Operator Display http nicontrols com ...
Page 75: ...64 ACS 400 User s Manual http nicontrols com ...
Page 161: ...150 ACS 400 User s Manual http nicontrols com ...
Page 167: ...156 ACS 400 User s Manual http nicontrols com ...
Page 177: ...166 ACS 400 User s Manual http nicontrols com ...
Page 179: ...168 ACS 400 User s Manual ACS 400 NEMA Type 1 Enclosure R2 Frame Size http nicontrols com ...
Page 180: ...ACS 400 User s Manual 169 ACS 400 NEMA Type 1 Enclosure R3 Frame Size http nicontrols com ...
Page 181: ...170 ACS 400 User s Manual ACS 400 NEMA Type 1 Enclosure R4 Frame Size http nicontrols com ...
Page 182: ...ACS 400 User s Manual 171 ACS 400 NEMA Type 12 4 Enclosure R1 Frame Size http nicontrols com ...
Page 183: ...172 ACS 400 User s Manual ACS 400 NEMA 12 4 Enclosure R2 Frame Size http nicontrols com ...
Page 184: ...ACS 400 User s Manual 173 ACS 400 NEMA Type 12 4 R3 Frame Size http nicontrols com ...
Page 185: ...174 ACS 400 User s Manual ACS 400 NEMA Type 12 4 R4 Frame Size http nicontrols com ...
Page 186: ...http nicontrols com ...