4.
Align the transport units and verify the following:
• Maximum values for the axial misalignment and the angular
deflection of two adjoining water pipes are not exceeded.
Axial misalignment: ± 3 mm
Axial deflection: 5°
• Bolt holes are aligned where transport units are joined (see the
connection points on Fig. 5-1)
• Cabinet doors are not misaligned and that there are no gaps
between cabinet walls and cabinet frame
• Adjoining surfaces of transport units meet perfectly all around