7.7.1.2. Preparing cables for EMC plates
1.
Remove the grommets.
2.
To ensure proper sealing, cut along the marking that corresponds to the cable
diameter and slide the grommet onto the cable.
NOTE – The grommet must fit tightly to prevent water entering the cabinet.
The grommets can be discarded if cables are entered through the floor.
3.
If necessary, remove the entry plate and pull the cable through the entry holes.
4.
Loosen the screws of the EMC cushion brackets and push the cushions apart
(arrows).
5.
If the outer cable screen is non-conductive, cut open the cable screen in the
middle of the stripped area (1), pull the screen ends over the cable insulation
(2) and then connect the screen ends with a continuous conducting foil (3).
Figure 7
-
18 Preparing control cables for EMC plates
1
2
2
3