07 ELECTRICAL INSTALLATION
3BHS206977 E01 REV H
ACS1000I AIR-COOLED
USER MANUAL
98/174
Figure 7-6: Bolt locations on terminal compartment roof for the galvanized steel plate
Note:
If the input voltage of the drive is higher than 6.9 kV, continue with the following
steps, ie, “7.5.4.1 Installing the insulating barrier for bottom cable entry” on page 98
7.5.4.1
Installing the insulating barrier for bottom cable entry
1. Remove the protective film from the insulating barrier.
2. Fasten three brackets to the insulating barrier in the locations indicated in Fig. 7-7.
Figure 7-7: Bracket location on insulating barrier
(1) Bolt location
(2) Bolt location
(3) Galvanized steel plate
(4) 3x M6x16
(5) 3x M6
1
1
1
2
2
2
3
4
5
(1) 3x M6x12 (self-tapping)
1
Summary of Contents for ACS1000i air-cooled
Page 1: ... MEDIUM VOLTAGE AC DRIVES ACS1000i air cooled User manual ...
Page 3: ...Contents ACS1000i air cooled User manual ...
Page 5: ... 01 About this manual 01 5 16 ...
Page 16: ......
Page 17: ... 02 Important safety information 02 17 28 ...
Page 28: ......
Page 29: ... 03 Power electronics and cabinet features03 29 56 ...
Page 57: ... 04 Control system 04 57 70 ...
Page 71: ... 05 Transportation storage and disposal05 71 78 ...
Page 78: ......
Page 79: ... 06 Mechanical installation 06 79 88 ...
Page 88: ......
Page 89: ... 07 Electrical installation07 89 104 ...
Page 105: ... 08 Commissioning 08 105 110 ...
Page 110: ......
Page 111: ... 09 Operation 09 111 124 ...
Page 125: ... 10 CDP control panel 10 125 148 ...
Page 149: ... 11 Preventive and corrective maintenance 11 149 172 ...
Page 173: ......