3AUA0000156966 REV A EN 6.5.2015

2108=

“Auto-0” 

(Auto-run, default)

Drive in terminal mode
1103=0

The enable signal input (usually digital input 1) is configured 
to be automatically recognised and is not required to be re-
asserted following a trip or a power-up in order to start the 
drive. If the run input is closed prior to the mains power being 
applied to the ACS250, and remains closed while the drive is 
powered up, the ACS250 will start. 

“Auto-0” is normally used where access to the enable input is 
restricted and the drive needs to run as soon as mains power 
is applied. It must only be used where this form of start up 
presents no danger to personnel or equipment in the vicinity 
of any moving or electrical parts. 

Drive in keypad mode
1103=1 or 2

The enable signal input must always by present in order for 
the drive to run. The drive will power up in a stop condition 
and the start button on the keypad will control drive start. 
Removal of the enable input will cause the drive to stop. While 
the enable is present normal start/stop behavior is controlled 
by the start and stop keys on the keypad.  

2108=

“Auto-1”, “Auto-2”, “Auto-3”, “Auto-4”, “Auto-5”

In this mode, the operation is similar to “Auto-0”, except 
that the user can define how many times the drive will 
automatically attempt to clear a trip and restart before 
permanently tripping and requiring a manual reset. The drive 
will make between 1 (“Auto-1”) and 5 (“Auto-5”) automatic 
attempts to clear the trip and restart. 

The delay between restart attempts is set at 20 seconds.  

The restart attempt counter (1-5) is reset by any of the 
following operation.

 

– Powering the drive down and back up again.

 

– Pressing the reset (stop) button on the drive keypad when 

the drive is tripped (displaying a trip message).

 

– Removing and reapplying the hardware enable signal.

1100 Keypad mode restart speed

These values apply only when the drive is running in keypad 
mode, 1103= 1 or 2.

Minimum speed
1100=0

The ACS250 will automatically run at the minimum 
programmed frequency (value entered into parameter 2007) 
when started from the keypad, regardless of the speed it was 
previously running at prior to a stop or power off condition 
being applied. With minimum speed (2007) set to 0 the drive 
will always restart with a set point speed of 0. 

Previous operating speed
1100=1

The ACS250 will automatically run at the previous speed set 
point, prior to the stop condition being applied, when started 
from the keypad. This applies both to the drive being stopped 
and to the mains input power being removed (previous set 
point is retained on power off). E.g. with the drive powered 
off while running at 20 Hz, the next start after power on will 
cause the drive to run immediately up to 20 Hz.  

Current running speed
1100=2

This mode of operation is used where the drive has other 
speed references signals that can be selected by the user in 
addition to keypad operation. When set to ‘current running 
speed’ the drive will maintain its current operating speed 
when switching back into keypad mode.

For example, if the drive was running in preset speed mode 
at a speed of 35 Hz and is switched from preset speed 
mode into keypad mode then keypad mode operation would 
commence at 35 Hz. If ‘current running speed’ was not 
selected (in 1100) then the drive would revert to operating at 
the start up speed defined by 1100.

Preset speed 4
1100=3

The ACS250 will automatically run at the frequency 
programmed into preset speed 4 (value entered into 
parameter 1205) when started from the keypad, regardless of 
the speed it was previously running at prior to a stop or power 
off condition being applied. With preset speed 4 (1205) set to 
0 the drive will always restart with a set point speed of 0.

For more information please contact 
your local ABB representative or visit:

www.abb.com/drives