45
Parameters in the Long parameter mode
Index
Name/Selection
Description
Def
1305
ANALOG INPUT 2 OFFSET
Sets an offset, as a percentage of the full scale range of the input, which is applied to the
analog input signal
0.0%
-500…500 %
Value in percent of the full scale range of the input
Example: If the analog input signal format is 0-10V, offset = 20% .
An analog input signal level of 7 Volts gives the following result :-
Analog input level (%) = 7/10 = 70%
Result = 70-20 (%) = 50%
1307
ANALOG INPUT 2 SCALING
Scales the analog input by this factor, (as a percentage of the full scale range of this input).
100.0%
0.0…2000.0 %
Example: If parameter 1304 ANALOG INPUT 2 FORMAT is set for 0 – 10V, and the scaling
factor is set to 200.0%, a 5 volt input will result in the drive running at maximum speed as set
in parameter 2008 MAX SPEED LIMIT
14
RELAY OUTPUTS
Status information indicated through relay output and relay operating delays
1401
USER RELAY 1 OUTPUT
(TERMINALS 14, 15 & 16)
FUNCTION SELECT
Selects the function assigned to Relay Output 1. The relay has three output terminals, Logic 1
indicates the relay is active, and therefore terminals 14 and 15 will be linked together.
Note : When using settings 4 – 7, parameters 3203 USER RELAY 1 UPPER LIMIT and 3202
USER RELAY 1 LOWER LIMIT must be used together to control the behavior. The output will
switch to Logic 1 when the selected signal exceeds the value programmed in parameter 3203
USER RELAY 1 UPPER LIMIT, and return to Logic 0 when the signal falls below the value
programmed in parameter 3202 USER RELAY 1 LOWER LIMIT.
1: Drive
Ready
0 : DRIVE ENABLED
(RUNNING).
Logic 1 when the motor is enabled.
1: DRIVE READY
Logic 1 when power is applied to the drive and no fault exists.
2 : AT TARGET FREQUENCY
(SPEED)
Logic 1 when the output frequency matches the setpoint frequency.
3: OUTPUT FREQUENCY >
0.0 HZ
Logic 1 when the drive output frequency to the motor is exceeds 0.0Hz.
4 : OUTPUT FREQUENCY
>= LIMIT
Logic 1 when the motor speed exceeds the adjustable limit. (See note above)
5 : OUTPUT CURRENT >=
LIMIT
Logic 1 when the motor current exceeds the adjustable limit. (See note above)
6 : OUTPUT TORQUE >=
LIMIT
Logic 1 when the motor torque exceeds the adjustable limit. (See note above)
7 : ANALOG INPUT 2
SIGNAL LEVEL >= LIMIT.
Logic 1 when the signal applied to the Analog Input 2 exceeds the adjustable limit. (See note
above)
8 : RESERVED
No Function
9 : RESERVED
No Function
10 : RESERVED
No Function
11 : RESERVED
No Function
12 : DRIVE TRIPPED
Logic 1 when the drive has tripped and the display shows the fault code.
13 : STO STATUS.
Logic 1 when both STO inputs are present and the drive is able to be operated.
1402
USER RELAY 2 OUTPUT
(TERMINALS 17 & 18)
FUNCTION SELECT
Selects the function assigned to Relay Output 2. The relay has three output terminals, Logic 1
indicates the relay is active, and therefore terminals 17 and 18 will be linked together.
Note : When using settings 4 – 7, parameters 3206 USER RELAY 2 UPPER LIMIT and 3205
USER RELAY 2 LOWER LIMIT must be used together to control the behaviour. The output will
switch to Logic 1 when the selected signal exceeds the value programmed in parameter 3206
USER RELAY 2 UPPER LIMIT, and return to Logic 0 when the signal falls below the value
programmed in parameter 3205 USER RELAY 2 LOWER LIMIT.
0 : Drive
Enabled
(Running).
Logic 1
when the
motor is
enabled
1: DRIVE READY
Logic 1 when power is applied to the drive and no fault exists
2 : AT TARGET FREQUENCY
(SPEED)
Logic 1 when the output frequency matches the setpoint frequency
3: OUTPUT FREQUENCY
> 0.0 HZ
Logic 1 when the drive output frequency to the motor is exceeds 0.0Hz
4 : OUTPUT FREQUENCY
>= LIMIT
Logic 1 when the motor speed exceeds the adjustable limit
5 : OUTPUT CURRENT
>= LIMIT
Logic 1 when the motor current exceeds the adjustable limit
6 : OUTPUT TORQUE >=
LIMIT
Logic 1 when the motor torque exceeds the adjustable limit
7 : ANALOG INPUT 2
SIGNAL LEVEL >= LIMIT
1 Logic when the signal applied to the Analog Input 2 exceeds the adjustable limit