Actual signals and parameters
157
5127
FBA PAR REFRESH
Validates any changed adapter module configuration parameter
settings.
52
PANEL COMM
Communication settings for the control panel port on the drive
5201
STATION ID
Defines the address of the drive.
1
5202
BAUD RATE
Defines the transfer rate of the link.
39242
5203
PARITY
Defines the use of parity and stop bit(s).
8 NONE 1
5204
OK MESSAGES
Number of valid messages received by the drive.
0
5205
PARITY ERRORS
Number of characters with a parity error received from the
Modbus link.
0
5206
FRAME ERRORS
Number of characters with a framing error received by the
Modbus link.
0
5207
BUFFER OVERRUNS
Number of characters which overflow the buffer, i.e. number of
characters which exceed the maximum message length, 128
bytes.
0
5208
CRC ERRORS
Number of messages with an CRC (cyclic redundancy check)
error received by the drive.
0
53
EFB PROTOCOL
Embedded fieldbus link settings.
5302
EFB STATION ID
Defines the address of the device.
1
5303
EFB BAUD RATE
Defines the transfer rate of the link.
39242
5304
EFB PARITY
Defines the use of parity and stop bit(s) and the data length.
8 NONE 1
5305
EFB CTRL PROFILE
Selects the communication profile.
ABB DRV LIM
5306
EFB OK MESSAGES
Number of valid messages received by the drive.
0
5307
EFB CRC ERRORS
Number of messages with an CRC (cyclic redundancy check)
error received by the drive.
0
5310
EFB PAR 10
Selects an actual value to be mapped to Modbus register 40005.
0
5311
EFB PAR 11
Selects an actual value to be mapped to Modbus register 40006.
0
5312
EFB PAR 12
Selects an actual value to be mapped to Modbus register 40007.
0
5313
EFB PAR 13
Selects an actual value to be mapped to Modbus register 40008.
0
5314
EFB PAR 14
Selects an actual value to be mapped to Modbus register 40009.
0
5315
EFB PAR 15
Selects an actual value to be mapped to Modbus register 40010.
0
5316
EFB PAR 16
Selects an actual value to be mapped to Modbus register 40011.
0
5317
EFB PAR 17
Selects an actual value to be mapped to Modbus register 40012.
0
5318
EFB PAR 18
Reserved
0
5319
EFB PAR 19
ABB Drives profile (ABB DRV LIM or ABB DRV FULL) Control
Word. Read only copy of the Fieldbus Control Word.
0x0000
5320
EFB PAR 20
ABB Drives profile (ABB DRV LIM or ABB DRV FULL) Status
Word. Read only copy of the Fieldbus Status Word.
0x0000
54
FBA DATA IN
Data from drive to fieldbus controlle.
5401
FBA DATA IN 1
Selects data to be transferred from the drive to the fieldbus
controller.
5402
FBA DATA IN 2
See 5401 FBA DATA IN 1.
....
...
...
5410
FBA DATA IN 10
See 5401 FBA DATA IN 1.
55
FBA DATA OUT
Data from fieldbus controller to drive.
5501
FBA DATA OUT 1
Selects data to be transferred from the fieldbus controller to the
drive.
5502
FBA DATA OUT 2
See 5501 FBA DATA OUT 1.
...
...
...
5510
FBA DATA OUT 10
See 5501 FBA DATA OUT 1.
84
SEQUENCE PROG
Sequence programming.
8401
SEQ PROG ENABLE
Enables sequence programming.
DISABLED
8402
SEQ PROG START
Selects the source for the sequence programming activation
signal.
NOT SEL
Parameters – short form list
Index
Name/Selection
Description
Def
Custom
Summary of Contents for ACS350 Series
Page 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Page 4: ......
Page 8: ...Safety 8 ...
Page 18: ...Table of contents 18 ...
Page 24: ...Hardware description 24 ...
Page 44: ...Installation checklist 44 ...
Page 56: ...Start up control with I O and ID Run 56 ...
Page 140: ...Program features 140 ...
Page 242: ...Actual signals and parameters 242 ...
Page 266: ...Fieldbus control with embedded fieldbus 266 ...
Page 284: ...Fault tracing 284 ...
Page 288: ...Maintenance and hardware diagnostics 288 ...
Page 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Page 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Page 313: ......