Actual signals and parameters
164
COMM
REF1 SELECT.
8
COMM+AI1
REF1 SELECT.
9
COMM*AI1
REF1 SELECT.
10
DI3U,4D(RNC)
REF1 SELECT.
11
DI3U,4D(NC)
REF1 SELECT.
12
AI1+AI2
REF1 SELECT.
14
AI1*AI2
REF1 SELECT.
15
AI1-AI2
REF1 SELECT.
16
AI1/AI2
REF1 SELECT.
17
PID1OUT
PID controller 1 output. See parameter groups
and
19
DI4U,5D
REF1 SELECT.
30
DI4U,5D(NC)
REF1 SELECT.
31
FREQ INPUT
REF1 SELECT.
32
SEQ PROG
REF1 SELECT.
33
AI1+SEQ PROG
REF1 SELECT.
34
AI2+SEQ PROG
REF1 SELECT.
35
1107
REF2 MIN
Defines the minimum value for external reference REF2. Corresponds to the
minimum setting of the used source signal.
0
0.0…100.0%
Value in percent of the maximum frequency / maximum speed / nominal
torque. See example in parameter
REF1 MIN for correspondence to the
source signal limits.
1 = 0.1%
1108
REF2 MAX
Defines the maximum value for external reference REF2. Corresponds to the
maximum setting of the used source signal.
100
0.0…100.0%
Value in percent of the maximum frequency / maximum speed / nominal
torque. See example in parameter
REF1 MIN for correspondence to the
source signal limits.
1 = 0.1%
12 CONSTANT SPEEDS
Constant speed selection and values. See section
page
1201
CONST SPEED SEL
Activates the constant speeds or selects the activation signal.
DI3,4
NOT SEL
No constant speed in use
0
DI1
Speed defined by parameter
CONST SPEED 1 is activated through
digital input DI1. 1 = active, 0 = inactive.
1
DI2
Speed defined by parameter
CONST SPEED 1 is activated through
digital input DI2. 1 = active, 0 = inactive.
2
DI3
Speed defined by parameter
CONST SPEED 1 is activated through
digital input DI3. 1 = active, 0 = inactive.
3
DI4
Speed defined by parameter
CONST SPEED 1 is activated through
digital input DI4. 1 = active, 0 = inactive.
4
DI5
Speed defined by parameter
CONST SPEED 1 is activated through
digital input DI5. 1 = active, 0 = inactive.
5
Parameters – complete descriptions
Index Name/Selection
Description
Def, FbEq
Summary of Contents for ACS350 Series
Page 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Page 4: ......
Page 8: ...Safety 8 ...
Page 18: ...Table of contents 18 ...
Page 24: ...Hardware description 24 ...
Page 44: ...Installation checklist 44 ...
Page 56: ...Start up control with I O and ID Run 56 ...
Page 140: ...Program features 140 ...
Page 242: ...Actual signals and parameters 242 ...
Page 266: ...Fieldbus control with embedded fieldbus 266 ...
Page 284: ...Fault tracing 284 ...
Page 288: ...Maintenance and hardware diagnostics 288 ...
Page 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Page 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Page 313: ......