Actual signals and parameters
165
DI1,2
Constant speed selection through digital inputs DI1 and DI2.1 = DI active,
0 = DI inactive.
7
DI2,3
See selection DI1,2.
8
DI3,4
See selection DI1,2.
9
DI4,5
See selection DI1,2.
10
DI1,2,3
Constant speed selection through digital inputs DI1, DI2 and DI3. 1 = DI
active, 0 = DI inactive.
12
DI3,4,5
See selection DI1,2,3.
13
TIMED FUNC 1
CONST SPEED 1 is activated by timed
function. Timed function 1 active = CONST SPEED 1. See parameter group
15
TIMED FUNC 2
See selection TIMED FUNC 1.
16
TIMED FUNC 3
See selection TIMED FUNC 1.
17
TIMED FUNC 4
See selection TIMED FUNC 1.
18
TIMED FUN1&2
Speed selection with TIMED FUNC 1 and TIMED FUNC 2. See parameter
TIMED MODE SEL.
19
DI1(INV)
Speed defined by parameter
CONST SPEED 1 is activated through
inverted digital input DI1. 0 = active, 1 = inactive.
-1
DI2(INV)
Speed defined by parameter
CONST SPEED 1 is activated through
inverted digital input DI2. 0 = active, 1 = inactive.
-2
DI3(INV)
Speed defined by parameter
CONST SPEED 1 is activated through
inverted digital input DI3. 0 = active, 1 = inactive.
-3
DI4(INV)
Speed defined by parameter
CONST SPEED 1 is activated through
inverted digital input DI4. 0 = active, 1 = inactive.
-4
DI5(INV)
Speed defined by parameter
CONST SPEED 1 is activated through
inverted digital input DI5. 0 = active, 1 = inactive.
-5
DI1,2(INV)
Constant speed selection through inverted digital inputs DI1 and DI2. 1 = DI
active, 0 = DI inactive.
-7
Parameters – complete descriptions
Index Name/Selection
Description
Def, FbEq
DI1
DI2 Operation
0
0
No constant speed
1
0
Speed defined by parameter
CONST SPEED 1
0
1
Speed defined by parameter
CONST SPEED 2
1
1
Speed defined by parameter
CONST SPEED 3
DI1 DI2
DI3 Operation
0
0
0
No constant speed
1
0
0
0
1
0
1
1
0
0
0
1
1
0
1
0
1
1
1
1
1
DI1 DI2 Operation
1
1 No constant speed
0
1 Speed defined by parameter
CONST SPEED 1
1
0 Speed defined by parameter
CONST SPEED 2
0
0 Speed defined by parameter
CONST SPEED 3
Summary of Contents for ACS350 Series
Page 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Page 4: ......
Page 8: ...Safety 8 ...
Page 18: ...Table of contents 18 ...
Page 24: ...Hardware description 24 ...
Page 44: ...Installation checklist 44 ...
Page 56: ...Start up control with I O and ID Run 56 ...
Page 140: ...Program features 140 ...
Page 242: ...Actual signals and parameters 242 ...
Page 266: ...Fieldbus control with embedded fieldbus 266 ...
Page 284: ...Fault tracing 284 ...
Page 288: ...Maintenance and hardware diagnostics 288 ...
Page 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Page 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Page 313: ......