Actual signals and parameters
234
DO=1
Transistor output is energized (closed) and relay output is de-energized.
Analog output control is frozen to the previously set value.
-0.2
RO=1
Transistor output is de-energized (opened) and relay output is energized.
Analog output control is frozen to the previously set value.
-0.1
AO=0
Analog output value is set to zero. Relay and transistor outputs are frozen to
the previously set value.
0.0
0.1…100.0%
Value written to signal
SEQ PROG AO VAL. Value can be connected to
control analog output AO by setting parameter
AO1 CONTENT SEL
value to 170 (i.e. signal 0170 SEQ PROG AO VAL). AO value is frozen to this
value until it is zeroed.
8424
ST1 CHANGE DLY
Defines the delay time for state 1. When delay has elapsed, state transition is
allowed. See parameters
ST1 TRIG TO ST 2 and
ST1 TRIG TO
ST N.
0
0.0…6553.5 s
Delay time
1 = 0.1 s
8425
ST1 TRIG TO ST 2
Selects the source for the trigger signal, which changes the state from state 1
to state 2.
Note:
State change to state N (8426 ST1 TRIG TO ST N) has a higher
priority than state change to the next state (8425 ST1 TRIG TO ST 2).
NOT SEL
DI5(INV)
Trigger through inverted digital input DI5. 0 = active, 1 = inactive.
-5
DI4(INV)
See selection DI5(INV).
-4
DI3(INV)
See selection DI5(INV).
-3
DI2(INV)
See selection DI5(INV).
-2
DI1(INV)
See selection DI5(INV).
-1
NOT SEL
No trigger signal. If parameter
ST1 TRIG TO ST N setting is also NOT
SEL, the state is frozen and can be reset only with parameter
SEQ
PROG START.
0
DI1
Trigger through digital input DI1. 1 = active, 0 = inactive.
1
DI2
See selection DI1.
2
DI3
See selection DI1.
3
DI4
See selection DI1.
4
DI5
See selection DI1.
5
AI 1 LOW 1
State change when AI1 value < par.
SEQ VAL 1 LOW value.
6
AI 1 HIGH 1
State change when AI1 value > par.
SEQ VAL 1 HIGH value.
7
AI 2 LOW 1
State change when AI2 value < par.
SEQ VAL 1 LOW value.
8
AI 2 HIGH 1
State change when AI2 value > par.
SEQ VAL 1 HIGH value.
9
AI1 OR 2 LO1
State change when AI1 or AI2 value < par.
SEQ VAL 1 LOW value.
10
AI1LO1AI2HI1
State change when AI1 value < par.
SEQ VAL 1 LOW value and AI2
SEQ VAL 1 HIGH value.
11
AI1LO1 ORDI5
State change when AI1 value < par.
SEQ VAL 1 LOW value or when
DI5 is active.
12
AI2HI1 ORDI5
State change when AI2 value > par.
SEQ VAL 1 HIGH value or when
DI5 is active.
13
AI 1 LOW 2
State change when AI1 value < par.
SEQ VAL 2 LOW value.
14
AI 1 HIGH 2
State change when AI1 value > par.
SEQ VAL 2 HIGH value.
15
AI 2 LOW 2
State change when AI2 value < par.
SEQ VAL 2 LOW value.
16
Parameters – complete descriptions
Index Name/Selection
Description
Def, FbEq
Summary of Contents for ACS350 Series
Page 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Page 4: ......
Page 8: ...Safety 8 ...
Page 18: ...Table of contents 18 ...
Page 24: ...Hardware description 24 ...
Page 44: ...Installation checklist 44 ...
Page 56: ...Start up control with I O and ID Run 56 ...
Page 140: ...Program features 140 ...
Page 242: ...Actual signals and parameters 242 ...
Page 266: ...Fieldbus control with embedded fieldbus 266 ...
Page 284: ...Fault tracing 284 ...
Page 288: ...Maintenance and hardware diagnostics 288 ...
Page 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Page 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Page 313: ......