Actual signals and parameters
226
5303
EFB BAUD RATE
Defines the transfer rate of the link.
9.6
9.6
9.6 kbit/s
1 = 0.1 kbit/s
19.2
19.2 kbit/s
38.4
38.4 kbit/s
57.6
57.6 kbit/s
115.2
115.2 kbit/s
5304
EFB PARITY
Defines the use of parity and stop bit(s) and the data length. The same
setting must be used in all on-line stations.
8 NONE 1
8 NONE 1
No parity bit, one stop bit, 8 data bits
0
8 NONE 2
No parity bit, two stop bits, 8 data bits
1
8 EVEN 1
Even parity indication bit, one stop bit, 8 data bits
2
8 ODD 1
Odd parity indication bit, one stop bit, 8 data bits
3
5305
EFB CTRL PROFILE
Selects the communication profile. See section
page
ABB DRV
LIM
ABB DRV LIM
ABB Drive limited profile
0
DCU PROFILE
DCU profile
1
ABB DRV FULL
ABB Drives profile
2
5306
EFB OK MESSAGES
Number of valid messages received by the drive. During normal operation,
this number increases constantly.
0
0...65535
Number of messages
1 = 1
5307
EFB CRC ERRORS
Number of messages with an CRC (cyclic redundancy check) error received
by the drive. If the number is high, check CRC calculation for possible errors.
Note:
High electromagnetic noise levels generate errors.
0
0...65535
Number of messages
1 = 1
5310
EFB PAR 10
Selects an actual value to be mapped to Modbus register 40005.
0
0...65535
Parameter index
1 = 1
5311
EFB PAR 11
Selects an actual value to be mapped to Modbus register 40006.
0
0...65535
Parameter index
1 = 1
5312
EFB PAR 12
Selects an actual value to be mapped to Modbus register 40007.
0
0...65535
Parameter index
1 = 1
5313
EFB PAR 13
Selects an actual value to be mapped to Modbus register 40008.
0
0...65535
Parameter index
1 = 1
5314
EFB PAR 14
Selects an actual value to be mapped to Modbus register 40009.
0
0...65535
Parameter index
1 = 1
5315
EFB PAR 15
Selects an actual value to be mapped to Modbus register 40010.
0
0...65535
Parameter index
1 = 1
5316
EFB PAR 16
Selects an actual value to be mapped to Modbus register 40011.
0
0...65535
Parameter index
1 = 1
5317
EFB PAR 17
Selects an actual value to be mapped to Modbus register 40012.
0
0...65535
Parameter index
1 = 1
Parameters – complete descriptions
Index Name/Selection
Description
Def, FbEq
Summary of Contents for ACS350 Series
Page 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Page 4: ......
Page 8: ...Safety 8 ...
Page 18: ...Table of contents 18 ...
Page 24: ...Hardware description 24 ...
Page 44: ...Installation checklist 44 ...
Page 56: ...Start up control with I O and ID Run 56 ...
Page 140: ...Program features 140 ...
Page 242: ...Actual signals and parameters 242 ...
Page 266: ...Fieldbus control with embedded fieldbus 266 ...
Page 284: ...Fault tracing 284 ...
Page 288: ...Maintenance and hardware diagnostics 288 ...
Page 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Page 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Page 313: ......