102 Control panels
Parameter backup mode
The Parameter backup mode is used to export parameters from one drive to another
or to make a backup of the drive parameters. Uploading to the panel stores all drive
parameters, including up to three user sets, to the assistant control panel. The full set,
partial parameter set (application) and user sets can then be downloaded from the
control panel to another drive or the same drive. Uploading and downloading can be
performed in local control.
The control panel memory is non-volatile and does not depend on the panel battery.
In the Parameter backup mode, you can:
• Copy all parameters from the drive to the control panel (UPLOAD TO PANEL).
This includes all defined user sets of parameters and internal (not adjustable by
the user) parameters such as those created by the ID run.
• View the information about the backup stored to the control panel with UPLOAD
TO PANEL (BACKUP INFO). This includes, for example, the type and rating of
the drive where the backup was made. It is useful to check this information when
you are going to copy the parameters to another drive with DOWNLOAD FULL
SET to ensure that the drives match.
• Restore the full parameter set from the control panel to the drive (DOWNLOAD
FULL SET). This writes all parameters, including the internal non-user-adjustable
motor parameters, to the drive. It does not include the user sets of parameters.
Note:
Only use this function to restore a drive from a backup or to transfer
parameters to systems that are identical to the original system.
• Copy a partial parameter set (part of the full set) from the control panel to a drive
(DOWNLOAD APPLICATION). The partial set does not include user sets, internal
motor parameters, parameters
…
,
, nor any group
and
parameters.
The source and target drives and their motor sizes do not need to be the same.
• Copy user set 1 parameters from the control panel to the drive (DOWNLOAD
USER SET1). A user set includes group
parameters and the
internal motor parameters.
The function is only shown on the menu when user set 1 has been first saved
using parameter
(see section
and then uploaded to the control panel with UPLOAD TO PANEL.
• Copy user set 2 parameters from the control panel to the drive (DOWNLOAD
USER SET2). As DOWNLOAD USER SET1 above.
• Copy user set 3 parameters from the control panel to the drive (DOWNLOAD
USER SET3). As DOWNLOAD USER SET1 above.
• Start, stop, change the direction and switch between local and remote control.
Summary of Contents for ACS355 series
Page 1: ...ABB machinery drives User s manual ACS355 drives ...
Page 4: ......
Page 16: ...16 ...
Page 32: ...32 Operation principle and hardware description ...
Page 58: ...58 Electrical installation ...
Page 74: ...74 Start up control with I O and ID run ...
Page 106: ...106 Control panels ...
Page 120: ...120 Application macros ...
Page 178: ...178 Program features ...
Page 338: ...338 Fieldbus control with embedded fieldbus ...
Page 368: ...368 Fault tracing ...
Page 404: ...404 Dimension drawings ...
Page 410: ...410 Appendix Resistor braking ...
Page 434: ...434 Appendix Permanent magnet synchronous motors PMSMs ...