212 Actual signals and parameters
DI1(INV)
User parameter set control through inverted digital input
DI1. Falling edge of inverted digital input DI1: User
parameter set 2 is loaded into use. Rising edge of inverted
digital input DI1: User parameter set 1 is loaded into use.
-1
DI2(INV)
See selection
-2
DI3(INV)
See selection
-3
DI4(INV)
See selection
-4
DI1,2(INV)
User parameter set selection through inverted digital inputs
DI1 and DI2. 1 = DI inactive, 0 =DI active.
-7
DI2,3(INV)
See selection
-8
DI3,4(INV)
See selection
-9
DI4,5(INV)
See selection
-10
1606 LOCAL LOCK
Disables entering local control mode or selects the source
for the local control mode lock signal. When local lock is
active, entering the local control mode is disabled
(LOC/REM key of the panel).
NOT SEL
Local control is allowed.
0
DI1
Local control mode lock signal through digital input DI1.
Rising edge of digital input DI1: Local control disabled.
Falling edge of digital input DI1: Local control allowed.
1
DI2
See selection
2
DI3
See selection
3
DI4
See selection
4
DI5
See selection
5
ON
Local control is disabled.
7
COMM
Fieldbus interface as the source for the local lock, ie,
Control word
bit 14. The Control
word is sent by the fieldbus controller through the fieldbus
adapter or embedded fieldbus (Modbus) to the drive. For
the Control word bits, see section
on page
.
Note:
This setting applies only for the DCU profile.
8
DI1(INV)
Local lock through inverted digital input DI1. Rising edge of
inverted digital input DI1: Local control allowed. Falling edge
of inverted digital input DI1: Local control disabled.
-1
DI2(INV)
See selection
-2
DI3(INV)
See selection
-3
All parameters
No.
Name/Value
Description
Def/FbEq
DI1
DI2 User parameter set
1
1
User parameter set 1
0
1
User parameter set 2
1
0
User parameter set 3
Summary of Contents for ACS355 series
Page 1: ...ABB machinery drives User s manual ACS355 drives ...
Page 4: ......
Page 16: ...16 ...
Page 32: ...32 Operation principle and hardware description ...
Page 58: ...58 Electrical installation ...
Page 74: ...74 Start up control with I O and ID run ...
Page 106: ...106 Control panels ...
Page 120: ...120 Application macros ...
Page 178: ...178 Program features ...
Page 338: ...338 Fieldbus control with embedded fieldbus ...
Page 368: ...368 Fault tracing ...
Page 404: ...404 Dimension drawings ...
Page 410: ...410 Appendix Resistor braking ...