Actual signals and parameters 235
2205 ACCELER
TIME 2
Defines the acceleration time 2, ie, the time required for the
speed to change from zero to the speed defined by
parameter
(in scalar control) /
(in vector control). The control mode is
.
See parameter
Acceleration time 2 is used also as jogging acceleration
time. See parameter
60.0 s
0.0…1800.0 s
Time
1 = 0.1 s
2206 DECELER
TIME 2
Defines the deceleration time 2, ie, the time required for the
speed to change from the value defined by parameter
(in vector control) to zero. The control mode is
.
See parameter
Deceleration time 2 is used also as jogging deceleration
time. See parameter
60.0 s
0.0…1800.0 s
Time
1 = 0.1 s
2207 RAMP SHAPE
2
Selects the shape of the acceleration/deceleration ramp 2.
The function is deactivated during emergency stop.
During jogging, parameter value is set to zero (ie, linear
ramp). See
.
0.0 = LINEAR
0.1…1000.0 s
See parameter
.
1 = 0.1 s
2208 EMERG DEC
TIME
Defines the time within which the drive is stopped if an
emergency stop is activated. See parameter
.
1.0 s
0.0…1800.0 s
Time
1 = 0.1 s
2209 RAMP INPUT 0 Defines the control for forcing the speed to 0 with the
currently used deceleration ramp (see parameters
and
).
NOT SEL
Not selected
0
DI1
Digital input DI1. Defines digital input
DI
1 as the control for
forcing the speed to zero.
• Activating the digital input forces the speed to zero, after
which the speed will stay at zero.
• De-activating the digital input: speed control resumes
normal operation.
1
DI2
See selection
.
2
DI3
See selection
.
3
DI4
See selection
.
4
DI5
See selection
.
5
All parameters
No.
Name/Value
Description
Def/FbEq
Summary of Contents for ACS355 series
Page 1: ...ABB machinery drives User s manual ACS355 drives ...
Page 4: ......
Page 16: ...16 ...
Page 32: ...32 Operation principle and hardware description ...
Page 58: ...58 Electrical installation ...
Page 74: ...74 Start up control with I O and ID run ...
Page 106: ...106 Control panels ...
Page 120: ...120 Application macros ...
Page 178: ...178 Program features ...
Page 338: ...338 Fieldbus control with embedded fieldbus ...
Page 368: ...368 Fault tracing ...
Page 404: ...404 Dimension drawings ...
Page 410: ...410 Appendix Resistor braking ...
Page 434: ...434 Appendix Permanent magnet synchronous motors PMSMs ...