290 Actual signals and parameters
5205 PARITY
ERRORS
Number of characters with a parity error received from the
Modbus link. If the number is high, check that the parity
settings of the devices connected on the bus are the same.
Note:
High electromagnetic noise levels generate errors.
0
0…65535
Number of characters
1 = 1
5206 FRAME
ERRORS
Number of characters with a framing error received by the
Modbus link. If the number is high, check that the
communication speed settings of the devices connected on
the bus are the same.
Note:
High electromagnetic noise levels generate errors.
0
0…65535
Number of characters
1 = 1
5207 BUFFER
OVERRUNS
Number of characters which overflow the buffer, ie, number
of characters which exceed the maximum message length,
128 bytes.
0
0…65535
Number of characters
1 = 1
5208 CRC ERRORS Number of messages with an CRC (cyclic redundancy
check) error received by the drive. If the number is high,
check CRC calculation for possible errors.
Note:
High electromagnetic noise levels generate errors.
0
0…65535
Number of messages
1 = 1
53 EFB PROTOCOL
Embedded fieldbus link settings. See chapter
control with embedded fieldbus
on page
.
5302 EFB STATION
ID
Defines the address of the device. Two units with the same
address are not allowed on-line.
1
0…247
Address
1 = 1
5303 EFB BAUD
RATE
Defines the transfer rate of the link.
1.2 kb/s
1.2 kbit/s
1 =
0.1 kbit/s
2.4 kb/s
2.4 kbit/s
4.8 kb/s 4.8
kbit/s
9.6 kb/s
9.6 kbit/s
19.2 kb/s
19.2 kbit/s
38.4 kb/s
38.4 kbit/s
57.6 kb/s
57.6 kbit/s
115.2 kb/s 115.2
kbit/s
5304 EFB PARITY
Defines the use of parity and stop bit(s) and the data length.
The same setting must be used in all on-line stations.
8 NONE 1
No parity bit, one stop bit, 8 data bits
0
8 NONE 2
No parity bit, two stop bits, 8 data bits
1
All parameters
No.
Name/Value
Description
Def/FbEq
Summary of Contents for ACS355 series
Page 1: ...ABB machinery drives User s manual ACS355 drives ...
Page 4: ......
Page 16: ...16 ...
Page 32: ...32 Operation principle and hardware description ...
Page 58: ...58 Electrical installation ...
Page 74: ...74 Start up control with I O and ID run ...
Page 106: ...106 Control panels ...
Page 120: ...120 Application macros ...
Page 178: ...178 Program features ...
Page 338: ...338 Fieldbus control with embedded fieldbus ...
Page 368: ...368 Fault tracing ...
Page 404: ...404 Dimension drawings ...
Page 410: ...410 Appendix Resistor braking ...
Page 434: ...434 Appendix Permanent magnet synchronous motors PMSMs ...