Actual signals and parameters 291
8 EVEN 1
Even parity indication bit, one stop bit, 8 data bits
2
8 ODD 1
Odd parity indication bit, one stop bit, 8 data bits
3
5305 EFB CTRL
PROFILE
Selects the communication profile. See section
on page
ABB DRV LIM
ABB drives limited profile
0
DCU PROFILE DCU profile
1
ABB DRV
FULL
ABB drives profile
2
5306 EFB OK
MESSAGES
Number of valid messages received by the drive. During
normal operation, this number increases constantly.
0
0…65535
Number of messages
1 = 1
5307 EFB CRC
ERRORS
Number of messages with an CRC (cyclic redundancy
check) error received by the drive. If the number is high,
check CRC calculation for possible errors.
Note:
High electromagnetic noise levels generate errors.
0
0…65535
Number of messages
1 = 1
5310 EFB PAR 10
Selects an actual value to be mapped to Modbus register
40005.
103
0…65535
Parameter index
1 = 1
5311 EFB PAR 11
Selects an actual value to be mapped to Modbus register
40006.
104
0…65535
Parameter index
1 = 1
5312 EFB PAR 12
Selects an actual value to be mapped to Modbus register
40007.
0
0…65535
Parameter index
1 = 1
5313 EFB PAR 13
Selects an actual value to be mapped to Modbus register
40008.
0
0…65535
Parameter index
1 = 1
5314 EFB PAR 14
Selects an actual value to be mapped to Modbus register
40009.
0
0…65535
Parameter index
1 = 1
5315 EFB PAR 15
Selects an actual value to be mapped to Modbus register
40010.
0
0…65535
Parameter index
1 = 1
5316 EFB PAR 16
Selects an actual value to be mapped to Modbus register
40011.
0
0…65535
Parameter index
1 = 1
5317 EFB PAR 17
Selects an actual value to be mapped to Modbus register
40012.
0
0…65535
Parameter index
1 = 1
All parameters
No.
Name/Value
Description
Def/FbEq
Summary of Contents for ACS355 series
Page 1: ...ABB machinery drives User s manual ACS355 drives ...
Page 4: ......
Page 16: ...16 ...
Page 32: ...32 Operation principle and hardware description ...
Page 58: ...58 Electrical installation ...
Page 74: ...74 Start up control with I O and ID run ...
Page 106: ...106 Control panels ...
Page 120: ...120 Application macros ...
Page 178: ...178 Program features ...
Page 338: ...338 Fieldbus control with embedded fieldbus ...
Page 368: ...368 Fault tracing ...
Page 404: ...404 Dimension drawings ...
Page 410: ...410 Appendix Resistor braking ...
Page 434: ...434 Appendix Permanent magnet synchronous motors PMSMs ...